![Omron C200HE-CPU11 Скачать руководство пользователя страница 99](http://html1.mh-extra.com/html/omron/c200he-cpu11/c200he-cpu11_installation-manual_742480099.webp)
87
5-2
Inspection and Maintenance
5-2-1 Replacing Output Unit Fuses
The following Output Units each contain one fuse. Replace the fuse if the fuse
indicator lights. The OD211, OD212, OA222, and OA224 Output Units do not
have fuse indicators. Replace the fuses on these Units if outputs are not pro-
duced.
Unit
Fuse indicator
Capacity
(20 mm long x 5.2 mm dia.)
C200H-OD411
Yes
125 V, 5 A
C200H-OD211
No
,
C200H-OD212
No
125 V, 8 A
C200H-OD213
Yes
,
C200H-OA221
Yes
250 V, 5 A
C200H-OA222V
No
250 V, 3 A
C200H-OA223
Yes
250 V, 5 A
C200H-OA224
No
250 V, 3.15 A
The OD411, OD213, OA221 and OA223 Output Units also provide an external
output bit that can be used to check the condition of the fuse. If bit 08 of the word
allocated to the Unit is ON, the fuse is burnt out.
To replace a fuse, follow the steps below. Use only UL/CSA certified replace-
ment fuses.
1, 2, 3...
1. Turn OFF the power to the PC.
2. Detach the terminal block by unlocking the lock levers at the top and bottom
of the terminal block.
3. While pushing down the lock lever on the Backplane with a screwdriver as
shown below, remove the Output Unit.
Lock lever
Inspection and Maintenance
Section 5-2
Содержание C200HE-CPU11
Страница 2: ...iv...
Страница 4: ...vi...
Страница 20: ......
Страница 60: ......
Страница 90: ......
Страница 106: ......
Страница 124: ......
Страница 201: ...Appendix B Specifications 189 Terminal Connections COM 12 to 24 VDC A0 A1 A2 A3 A4 A5 A6 A7 A8 A9 0 1 2 3 4 5 6 7 NC...
Страница 216: ......
Страница 222: ......
Страница 240: ......