53
gap of at least 80 mm between the top of the Power Supply Unit and the top of the
panel, wiring ducts, parts, or any other structures.
80 mm min.
80 mm min.
80 mm min.
80 mm min.
Ducts, etc.
C200HW-PA209R
Ducts, etc.
C200HW-PA209R
Ducts, etc.
3-1-3 Mounting Height
The mounting height of CPU Racks, Expansion I/O Racks, or Slave Racks is
118 mm or 153 mm depending on the type of I/O Units mounted. If Peripheral
Devices or connection cables are attached, the additional dimensions must be
taken into account. Allow sufficient clearance in the control panel in which the
PC is mounted.
118 to 153* mm
Approx. 180 to 223* mm
Note:
Figures marked with an asterisk are for
when the C200HW-PA209R is mounted.