91
OC224V
1
2
3
4
5
6
7
0
OC226
2
4
6
8
10
12
14
0
3
5
7
9
11
13
15
1
5-2-3 Batteries
DANGER
Batteries can burn, explode, or leak. Absolutely do not short-circuit across the
terminals, attempt to recharge batteries, or take them apart, heat them, or
expose them to fire.
When the battery is nearly discharged, the ERR indicator will flash and the mes-
sage “BATT FAIL” will appear on the Programming Console. When this occurs,
replace the battery within one week to avoid loss of data.
The normal battery service life is five years at 25
°
C. The service life will be
shorten if used at higher temperatures.
The Battery Fail Flag is allocated to 25308 for the C200HX/C200HG/C200HE.
The battery comes together with its connector as a set. To replace the Battery
Set (C200H-BAT09), follow the steps below. The entire replacement must be
completed within five minutes to ensure that the data will not be lost.
1, 2, 3...
1. Turn OFF the power to the PC. (If the power was not already ON, turn the
power ON for at least one minute before turning the power OFF.)
2. Remove the cover from the battery compartment of the CPU Unit.
3. Remove the old Battery Set.
4. Install the new Battery Set as shown in the following diagram.
Inspection and Maintenance
Section 5-2
Содержание C200HE-CPU11
Страница 2: ...iv...
Страница 4: ...vi...
Страница 20: ......
Страница 60: ......
Страница 90: ......
Страница 106: ......
Страница 124: ......
Страница 201: ...Appendix B Specifications 189 Terminal Connections COM 12 to 24 VDC A0 A1 A2 A3 A4 A5 A6 A7 A8 A9 0 1 2 3 4 5 6 7 NC...
Страница 216: ......
Страница 222: ......
Страница 240: ......