BU
1002
RW
2
14
2-3 Connecting the equipment
Caution
Do not connect devices with rated voltage of other than 200/208/220/230/
240/100VAC.
●
The rated output voltage of this device is 200/208/220/230/240/100VAC.
●
Overcurrent may damage the connected devices.
Caution
2-3-1. Connecting a device to the power supply output (AC output terminal block)
The output wiring work should be performed by a service person.
When in use, make sure the terminal block cover is attached. Do not turn
ON the power switch when it is detached.
●
Voltage is applied to the output terminal block when the power switch is ON, which can result in
electric shock.
When connecting a device to the output terminal block, make sure to
include an isolator switch or breaker between the unit and the load.
●
In the event of an accident, the power supply to the device can be stopped by pressing the iso-
lator switch or breaker.
●
To reduce the risk of fire, connect only to an isolator switch or breaker with a minimum rating
of 250V/15A. When the unit is used in compliance with UL standards or CE marking, follow the
National Electrical Code (ANSI/NFPA 70).
●
Install the isolator switch or breaker where it is easy to operate.
Isolator switch
or Breaker
d
a
o
L
S
P
U
G
L1
L2
(1) Connect the devices that require backup to the power supply output terminal block of the unit.
Attach two cable clamps to the terminal block cover with fasten torque according to Figure 1.
Run the wires to be connected through the hole in the terminal block cover (with cable clamp).
(See Figure 1.)
If you have trouble running the wire through the hole, loosen the cable clamp dial by turning it
counter-clockwise.
Use a flat head screwdriver to loosen the terminal block screws, insert the wire stripped to the
specified length into the terminal block from the bottom at an angle as far as it will go, and then
retighten the terminal block screws. (See Figure 2.)
G terminal : Connect the ground wire
L1 terminal : Connect the L1 line
L2 terminal : Connect the L2 line
Содержание BU1002RW
Страница 64: ...10 52 Notes of Chinese 10 UPS UPS 1 FA OA Windows UPS...
Страница 65: ...10 Notes of Chinese 53 2 FA OA 2...
Страница 66: ...BU1002RW 10 54 AC 50 60Hz AC AC AC AC...
Страница 67: ...10 Notes of Chinese 55 5cm 10cm UPS UPS AC AC AC200V 240V AC200 240V...
Страница 68: ...BU1002RW 10 56 AC AC AC AC AC ON OFF AC INPUT PROTECTION 25 5 2 5 35 3 5mA...
Страница 69: ...10 Notes of Chinese 57 AC UPS AC UPS...
Страница 70: ...BU1002RW 10 58 AC AC 50 60Hz 25 25 6 40 2 AC AC...
Страница 71: ...10 Notes of Chinese 59 DC250V UPS 200V http www fa omron com cn Pb AC AC 50 60Hz...
Страница 73: ...10 Notes of Chinese 61 3 UPS Instruction Manual 1 UPS UPS UPS UPS 2 UPS AC UPS AC UPS 3 UPS UPS ON UPS...