. Using the UPS monitoring software and contact signal
49
An additional contact signal card can be installed in the contact signal input/output slot on the back of
the UPS.
Contact signal card (model number: SC07), sold separately
Contact Signal
You can develop your unique system based on the following specifications to automate the pro-
cess at a power failure. You can perform power-failure processing by allowing the system to detect
the backup signal and also perform system shutdown processing by allowing the system to detect
the Low battery level signal. Also, by inputting the backup stop signal from the system, you can
stop the UPS with a sufficient battery level to prepare for the next occurrence of a power failure.
7-4-1. Signal output
The UPS has 4 kinds of output signals. The output circuit consists of an open collector circuit using
a photo coupler (a kind of electronic switch).
●
Backup Signal output: BU
Stays ON during backup operation at a power
failure.
●
Low battery level signal
output: BL
Goes ON when the battery becomes weak
during backup operation at a power failure.
●
Trouble Signal output: TR
Goes ON when an internal failure of the UPS
occurs or when the battery life counter
expires.
●
Battery Replacement Signal output (WB)
Goes ON when the test determines that bat-
tery replacement is necessary due to deterio-
ration or when the battery life counter goes
off-scale.
BU-COM ON when a power failure occurs
BL-COM ON when the battery is low
TR-COM ON when a power failure occurs
WB-COM ON when battery deterioration is detected
7-4-2. Signal input
●
Input of the UPS Stop Signal (BS)
When the BS signal is ON (High), the output of the UPS is stopped after the time period specified
in advance has elapsed. The following settings are available on the LCD.
(1) BS Valid Range: “Setting” - “Dry Contact” - “BSsignal ValidRange”
• Always enabled : The BS signal is received either in Commercial Power Mode or Battery Mode.
• Enabled during Battery Mode: The BS signal is received only in Battery Mode.
(2) BS Delay Time: “Setting” - “Dry Contact” - “BSsignal Delay Time”
You can set the amount of time between when the BS signal is received and when the output
of the UPS is stopped.
BS-COM
UPS stops
7-4 Contact signal
Содержание BN150R
Страница 69: ...57 Notes of Chinese 10 UPS UPS 1 FA OA Windows UPS...
Страница 70: ...BN75R BN150R BN300R 10 58 2 FA OA 2...
Страница 71: ...10 Troubleshooting 59 AC 50 60Hz AC AC AC AC 3P 2P AC AC...
Страница 72: ...BN75R BN150R BN300R 10 60 5cm UPS UPS AC AC AC200V 240V AC200 240V...
Страница 73: ...10 Troubleshooting 61 AC AC AC AC AC ON OFF AC INPUT PROTECTION 25 4 5 30 1mA...
Страница 74: ...BN75R BN150R BN300R 10 62 AC UPS AC UPS...
Страница 75: ...10 Troubleshooting 63 AC AC 50 60Hz 25 25 6 40 2 AC AC...
Страница 76: ...BN75R BN150R BN300R 10 64 DC250V UPS 200V http www fa omron com cn Pb AC AC 50 60Hz...
Страница 80: ...BN75R BN150R BN300R 68 BN300R 438 87 OMRON BN300R ESC 650...