Carry the unit considering its weight and balance, and place it on a stable
and robust base.
●
Dropping or toppling the unit may cause injury.
●
The approximate weights of the units are units are 13.5kg (BN75R), 21.5kg (BN150R) and 32kg
(BN300R).
●
If you drop the unit, stop using it and have it inspected and repaired.
For repair, contact us; ____
Do not hold the side of the front panel when lifting.
●
Injury may result if the panel comes off and falls.
Keep plastic package bags out of reach of children.
●
Children may suffocate if they place their heads into plastic bags.
Make sure to connect the unit’s AC input plug to a commercial power
source with rated input voltage (100 VAC) and 50/60Hz frequency.
●
Connecting to a commercial power source with a different rated input voltage or frequency may
result in a fire.
●
The unit may fail.
When an abnormality (unusual sound or smell) occurs, turn OFF the
unit’s power switch to stop the output, and stop the supply of commercial
power. Disconnect the AC input plug from the wall outlet.
The socket-outlet shall be installed near the equipment and shall be easily
accessible.
●
When performing maintenance on the connected devices, follow the above instructions to
ensure safety.
Do not connect devices such as dryers, some solenoid valves, etc. ,
which have a half-wave rectifier that allows only half-cycle AC power to
flow through.
●
Overcurrent may damage the UPS.
Connect the unit to a wall outlet (commercial power) with the appropriate
capacity (12A or greater for BN75R, 20A or greater for BN150R and 40A or
greater for BN300R.).
●
Otherwise, the power cord may be heated.
●
When equipment with the maximum output capacity is connected, a maximum current of 12A
(BN75R) or 20A (BN150R) or 40A (BN300R).
When changing the input cable for the BN150R/BN300R, perform
connection as specified.
Make sure to properly match the AC input terminal with the appropriate
wire color.
Do not perform work on the AC input terminal while the unit is connected
to a commercial power source.
●
Use an input cable that complies with the input current specification of the UPS.
●
Failure to do so may result in electric shock or ground fault.
Provide secure grounding.
●
After checking the plug shape of the wall outlet, directly connect the AC input plug of the unit to it.
A failure or leak that occurs when the unit is not properly grounded may result in electric shock.
2-1 Precautions and notes on installation and connection
Installation and connection
2
Caution
(for installation and connection)
Содержание BN150R
Страница 69: ...57 Notes of Chinese 10 UPS UPS 1 FA OA Windows UPS...
Страница 70: ...BN75R BN150R BN300R 10 58 2 FA OA 2...
Страница 71: ...10 Troubleshooting 59 AC 50 60Hz AC AC AC AC 3P 2P AC AC...
Страница 72: ...BN75R BN150R BN300R 10 60 5cm UPS UPS AC AC AC200V 240V AC200 240V...
Страница 73: ...10 Troubleshooting 61 AC AC AC AC AC ON OFF AC INPUT PROTECTION 25 4 5 30 1mA...
Страница 74: ...BN75R BN150R BN300R 10 62 AC UPS AC UPS...
Страница 75: ...10 Troubleshooting 63 AC AC 50 60Hz 25 25 6 40 2 AC AC...
Страница 76: ...BN75R BN150R BN300R 10 64 DC250V UPS 200V http www fa omron com cn Pb AC AC 50 60Hz...
Страница 80: ...BN75R BN150R BN300R 68 BN300R 438 87 OMRON BN300R ESC 650...