2-4 Connecting the AC input
When installation and connection are complete, connect the unit’s AC input to a commercial power
source.
Make sure to connect the AC input plug of the unit into a wall outlet
(commercial power) with rated input voltage (100V to 120V AC).
●
Connecting to a wall outlet (commercial power) of a different rated voltage may result in fire.
●
The unit may fail.
When the maximum output capacity (1500VA/1350W) is connected to the
BN150R, replace the AC input plug with a 20A plug. When the maximum
output capacity (3000VA/2700W) is connected to the BN300R, change to
terminal block connection.
●
Overheating or fire may occur if the power consumption exceeds the limits shown in the table
above.
●
If the maximum output capacity is being used, change the AC input connection method by refer-
ring to the table above.
●
After changing the AC input plug, change the “Setting” - “In/Out Settings” - “Input Plug” setting
in the menu on the LCD.
Caution
Caution
●
The BN75R AC input plug cannot be changed.
●
The AC input plug for the BN150R and BN300R can be changed according to the operating
environment.
●
The supported AC input plugs and the maximum connection capacities are as follows.
Change to an appropriate AC input plug according to the connection capacity of the device.
Model
AC input plug
Voltage sensitivity setting
Maximum connection capacity
BN75R
15A
Low
750VA/680W
Standard/High
750VA/680W
BN150R
15A (attached when shipped)
Low
1050VA/1050W
Standard/High
1125VA/1125W
20A
Low
1450VA/1350W
Standard/High
1500VA/1350W
BN300R
20A
Low
1420VA/1420W
Standard/High
1520VA/1520W
30A (attached when shipped)
Low
2220VA/2220W
Standard/High
2370VA/2370W
Terminal block connection
Low
3000VA/2700W
Standard/High
3000VA/2700W
* The bold font indicates factory settings.
Содержание BN150R
Страница 69: ...57 Notes of Chinese 10 UPS UPS 1 FA OA Windows UPS...
Страница 70: ...BN75R BN150R BN300R 10 58 2 FA OA 2...
Страница 71: ...10 Troubleshooting 59 AC 50 60Hz AC AC AC AC 3P 2P AC AC...
Страница 72: ...BN75R BN150R BN300R 10 60 5cm UPS UPS AC AC AC200V 240V AC200 240V...
Страница 73: ...10 Troubleshooting 61 AC AC AC AC AC ON OFF AC INPUT PROTECTION 25 4 5 30 1mA...
Страница 74: ...BN75R BN150R BN300R 10 62 AC UPS AC UPS...
Страница 75: ...10 Troubleshooting 63 AC AC 50 60Hz 25 25 6 40 2 AC AC...
Страница 76: ...BN75R BN150R BN300R 10 64 DC250V UPS 200V http www fa omron com cn Pb AC AC 50 60Hz...
Страница 80: ...BN75R BN150R BN300R 68 BN300R 438 87 OMRON BN300R ESC 650...