55
Connecting to the Network
Section 3-3
Note
The computer’s IP address is automatically displayed in the Host (PLC) Infor-
mation setting in the Setup Interface Dialog Box.
Setting the Network Address in the DeviceNet Unit Section Inside Remote
Information
Set the FINS network address of the DeviceNet Unit on the DeviceNet net-
work to be connected. Input if crossing networks past the direct Ethernet con-
nection. If not crossing networks, input 0.
Setting the Node Address in the DeviceNet Unit Section Inside Remote
Information
Set the node address of the DeviceNet Unit on the DeviceNet network to be
connected. Input if crossing networks past the direct Ethernet connection. If
not crossing networks, input 0.
Setting the Port No. in the Ethernet Unit Section Inside Remote
Information
Set the UDP port No. for FINS communication service by the Ethernet Unit.
Set it to the same value that is set in the CPU Bus Unit System Setting Area
inside the CPU Unit to which the Ethernet Unit is mounted. Normally, this set-
ting is 9600.
Setting the Unit. No in the DeviceNet Unit Section Inside Remote
Information
Set the unit No. (0 to F) of the DeviceNet Unit for CPU Bus Unit use on the
DeviceNet network to be connected.
Setting the IP Address in the Ethernet Unit Section Inside Remote
Information
Set the IP address for the Ethernet Unit. For the CS-series Ethernet Unit, the
value that is set with the rotary switch on the back of the Unit is input here. For
the CJ-series Ethernet Unit, the value that is set in the Allocated Words in the
DM Area, or in the System Setup for CPU Bus Units, is input here.
Note
For details on setting the IP address for the Ethernet Unit, refer to the SYS-
MAC CS/CJ-series Ethernet Units Operation Manual (catalog No. W343).
4.
Click the
Add
Button. The set value is registered and displayed in the Reg-
ister List.
• Registration Name: The registration name for the DeviceNet network to
be connected to.
• Node: The FINS network address and FINS node address. (The third
digit is always 0.)
• Unit: The FINS network address, FINS node address, and unit number of
the DeviceNet Unit.
Ethernet
CPU Unit
Ethernet Unit
Personal
computer
Obtain this value in
reverse from the
computer’s IP address,
by using the address
conversion of the
Ethernet Unit.
FINS node address
IP address
IP address
IP address
FINS message
IP address
FINS message
Address
conversion
FINS node address
This value (computer’s IP
address) is shown in the
host information.
Содержание 3G8E2-DRM21-EV1
Страница 3: ...iv ...
Страница 5: ...vi ...
Страница 9: ...x ...
Страница 13: ...xiv ...
Страница 19: ......
Страница 33: ...14 Operating Environment Section 1 3 ...
Страница 145: ......
Страница 161: ......
Страница 165: ......
Страница 167: ......
Страница 173: ......
Страница 175: ......
Страница 177: ......
Страница 179: ......
Страница 181: ......
Страница 187: ......