3-20
D
Solderless Terminals for Control Circuit Terminals
The use of solderless terminals for the control circuit terminals is recommended because solderless
terminals are easy to connect securely.
d1 dia.
d2 dia.
Wire thickness
Model
d1
d2
Manufacturer
Terminal
0.5 mm
2
A1 0.5-8WH
1.00
2.60
Phoenix Contact
SF, SR, S1 to
S3, SC, FS, FR,
FC
0.7 mm
2
A1 0.75-8GY
1.20
2.80
MA, MB, MC
1 mm
2
A1 1-8RD
1.40
3.00
,
,
D
Wiring Method
•
Wire each terminal as follows:
a) Loosen the terminal screw with a thin-slotted screwdriver.
b) Insert the wire from underneath the terminal block.
c) Tighten the terminal screw firmly.
•
Always separate the control signal line from the main circuit cables and other power cables.
•
Insulate the shielded sections with insulation tape, etc., from other signal lines or equipment and
ground on the Inverter side.
Thin-slotted screwdriver
Length of stripped
portion: Approx. 5.5 mm
Wire
Control circuit
terminal block
Do not solder this portion.
(Otherwise, faulty contact may result.)
Design
Chapter 3
Содержание 3G3EV-A2001-CUE
Страница 8: ......
Страница 9: ...INSTALLATION MANUAL Standard Multi function Model EC Directives Models SYSDRIVE 3G3EV Ajjjj CUE...
Страница 11: ...Chapter 1 Getting Started 1 1 Items to be Checked when Unpacking 1 2 Precautions 1...
Страница 14: ...Chapter 2 Overview 2 1 Features 2 2 Nomenclature 2...
Страница 19: ...Chapter 3 Design 3 1 Installation 3 2 Wiring 3...
Страница 41: ...Chapter 4 Specifications 4 1 Specifications of Main Unit 4 2 Specifications of Noise Filter 4...
Страница 48: ...4 8 D 3G3EV PNF2003A YN PNF2010A YN Two 5 0 dia max 1 Specifications Chapter 4...
Страница 49: ...4 9 D 3G3EV PNF2020A YN 5 0 dia 5 93 1 118 1 128 2 74 2 56 1 74 max Specifications Chapter 4...
Страница 50: ...4 10 D 3G3EV PNF3007C YN Four 5 0 dia 108 2 96 1 75 max 95 2 118 1 128 2 Specifications Chapter 4...