3-14
H
Conformance to LVD
Be sure to insert a molded-case circuit breaker (MCCB) into the power line connected to the Inverter for
short-circuit protection. A single MCCB is required by each Inverter.
The frequency reference power supply (FS) is basic isolation. Its insulation needs to be reinforced when
connecting to a peripheral device.
Inverter
MCCB
Model 3G3EV-
Rated current (A)
Type
A2001(M)-CUE
5
NF30 model (Mitsubishi Electric)
A2002(M)-CUE
5
(
)
A2004(M)-CUE
5
A2007(M)-CUE
10
A2015(M)-CUE
20
AB001(M)-CUE
5
NF30 model (Mitsubishi Electric)
AB002(M)-CUE
5
(
)
AB004(M)-CUE
10
AB007(M)-CUE
20
AB015(M)-CUE
20
A4002(M)-CUE
5
NF30 model (Mitsubishi Electric)
A4004(M)-CUE
5
(
)
A4007(M)-CUE
5
A4015(M)-CUE
10
H
Wiring on the Input Side of Main Circuit
D
Safe Power Supply Sequence
If a single MCCB is shared by more than one Inverter or other equipment, refer to the following and
provide a sequence that will turn off the power when abnormal output results.
3-phase/
single phase
200 VAC
Fault output (NC)
Fuse
Noise filter
L1 (R)
L2 (S)
L3 (T)
SYSDRIVE 3G3EV
Design
Chapter 3
Содержание 3G3EV-A2001-CUE
Страница 8: ......
Страница 9: ...INSTALLATION MANUAL Standard Multi function Model EC Directives Models SYSDRIVE 3G3EV Ajjjj CUE...
Страница 11: ...Chapter 1 Getting Started 1 1 Items to be Checked when Unpacking 1 2 Precautions 1...
Страница 14: ...Chapter 2 Overview 2 1 Features 2 2 Nomenclature 2...
Страница 19: ...Chapter 3 Design 3 1 Installation 3 2 Wiring 3...
Страница 41: ...Chapter 4 Specifications 4 1 Specifications of Main Unit 4 2 Specifications of Noise Filter 4...
Страница 48: ...4 8 D 3G3EV PNF2003A YN PNF2010A YN Two 5 0 dia max 1 Specifications Chapter 4...
Страница 49: ...4 9 D 3G3EV PNF2020A YN 5 0 dia 5 93 1 118 1 128 2 74 2 56 1 74 max Specifications Chapter 4...
Страница 50: ...4 10 D 3G3EV PNF3007C YN Four 5 0 dia 108 2 96 1 75 max 95 2 118 1 128 2 Specifications Chapter 4...