C1477B User Manual (UMC1477R01.pdf)
- 8 -
© Omniflex
Table 2-1: The Sequence Switch Settings
SEQUENCE
SW1
SEQ.
NO.
1 2 3
4
5
6
7
8
DESCRIPTION
Figure
In Section
ISA
DESIGNATION
T
TIME DELAY
0
0 0 0
0
0
SERVICE MODE (consult factory for service information)
-
1
1 0 0
0
0
LAMP FOLLOWS INPUT
1
--
--
2
0 1 0
0
0
MOMENTARY (FLEETING) ALARM, MANUAL RESET
2
M-1
--
3
1 1 0
0
0
ALARM ONLY (NON-LATCHING INPUTS) AUTO RESET
4
A-1-4
--
4
0 0 1
0
0
MOMENTARY ALARM, MANUAL RESET WITH ALARM RINGBACK
6
R-1-10
--
5
1 0 1
0
0
FIRST OUT, MULTIPLE GROUPS, MANUAL RESET
8
F2M-1
--
6
0 1 1
0
0
FIRST OUT, MANUAL RESET, AUTO RESET ON SUBSEQUENT ALARMS
9
F3A-1-3
--
7
1 1 1
0
0
FIRST OUT, SINGLE GROUP, MANUAL RESET, FIRST OUT CONTINUOUS FLASH
10
--
--
8
0 0 0
1
0
FIRST OUT, MANUAL RESET, SUBSEQUENT ALARMS WITHOUT HORN
11
F1M-1
--
9
1 0 0
1
0
MOMENTARY ALARM, MANUAL RESET, AUTO SILENCE AFTER TIME DELAY.
12
--
60 seconds
10
0 1 0
1
0
MOMENTARY ALARM, MANUAL RESET, REALARM AFTER TIME IF STILL
ABNORMAL.
13
--
60 seconds
11
1 1 0
1
0
MOMENTARY ALARM, MANUAL RESET, CONSTANT FLASH (FOR MOTOR ALARMS).
14
--
--
12
0 0 1
1
0
MOMENTARY ALARM, AUTO RESET, TIME DELAY ON RETURN TO NORMAL.
16
--
60 seconds
13
1 0 1
1
0
PULSE MONITORING ALARM; MANUAL RESET
17
--
--
17
1 1 1
1
0
INPUTS 1-4 SEQUENCE 1; INPUTS 5-8 SEQUENCE 27 (FOR MOTOR ALARMS)
1 & 25
--
18
0 1 0
0
1
MOMENTARY ALARM, AUTO RESET
18
--
--
21
1 0 1
0
1
FIRST OUT, MULTIPLE GROUPS, AUTO RESET
20
F2A-1
--
23
1 1 1
0
1
FIRST OUT, SINGLE GROUP, AUTO RESET, FIRST OUT CONTINUOUS FLASH
21
--
--
24
0 0 0
1
1
FIRST OUT, AUTO RESET, SUBSEQUENT ALARMS WITHOUT HORN
22
F1A-1
--
25
1 0 0
1
1
MOMENTARY ALARM, AUTO RESET, AUTO SILENCE AFTER TIME DELAY.
23
--
60 seconds
26
0 1 0
1
1
MOMENTARY ALARM, AUTO RESET, REALARM AFTER TIME IF STILL ABNORMAL.
24
--
60 seconds
27
1 1 0
1
1
MOMENTARY ALARM, AUTO RESET, CONSTANT FLASH (FOR MOTOR ALARMS)
25
--
--
29
1 0 1
1
1
PULSE MONITORING ALARM, AUTO RESET
27
--
--
FOLLOWS INPUT
0
0
FOLLOWS ALARM
STATE
1
0
NOTE:
FOLLOWS HORN
0
1
RELAY OUTPUT (see Section 2.4 for details)
In the above sequences, the switch
ACTS AS MRF
(REFLASH)
1
1
sense is as follows:
INPUT 8 AS NORMAL
0
WHEN THIS SWITCH IS ON, INPUT 8 MAY BE USED TO INHIBIT ALL OTHER ALARMS 1 TO 7.
“1” = switch in on position
INPUT 8 ACTS AS INHIBIT
1
IN THIS MODE LAMP 8 ON MEANS ANNUNCIATOR IS INHIBITED (see Section 2.5 for details).
“0” = switch in off position