4.4  Connecting the Relay 

The relay contact shown in the Figure 1-2 is shown with the relay coil in the de-energised state. 
i.e. with no power applied. The normally open contact refers to the relay convention of the 
contact in the de-energised state of the relay coil. In some of the modes of operation of this 
relay, the relay coil will be energised with no alarms present. The 

normal

 state of the 

system

 

would therefore be for the contact across the C and NO terminals of the relay to be 

closed.

 

4.5  Connecting the power supply 

Power supply connections are made to the plug-on terminals according to the following table: 

 

Table 2-3:  Power supply connections 

Supply 

Connector Terminals

 

Voltage 

14

 

15 

16 

dc 

Earth 

positive (+) 

negative (-) 

ac 

Earth 

Live 

Neutral 

 

5.  PREPARING THE BACKLIT DISPLAY LEGEND 

5.1  Overview 

Legends  are  created  for  the  Omni8

  on  a  laser  or  inkjet  printer  using  the  software 

templates provided with the product. 

Templates  for  popular  programs  are  supplied  on  a  CD  with  your  Omni8

.  These  are  for 

Microsoft Excel which is supported by all operating systems. There is also a README.TXT 
file  on  this  disk.  Run  this  first  to  see  which  version  of  program  you  must  run  to  use  the 
supplied templates. 

5.2  Creating the Legend Film 

To create the legend, open Excel and load the appropriate template supplied and then fill 
in your legend detail. Print it onto overhead transparency film (the type used for overhead 
presentations). A sheet is included with the product. Cut this along the cut marks which will 
print onto the film and then insert into the Omni8

(We  suggest  that  you  test  your  printout  on  plain-paper  first  to  ensure  that  all  aspects  of 
your Legend Film are to your liking before printing on to the actual film supplied.) 

Please  note  that  the  supplied  templates  have  been  tested  on  a  wide  range  of  printers. 
Your  particular  printer  may  scale  the  image  slightly  differently.  While  the  front  grid 
markings should accommodate this tolerance, in exceptional circumstances you may have 
to  alter  the  grid  spacing  on  the  template  supplied.  This  needs  to  be  done  once  only  and 
will then be set for your printer. 

5.3  Inserting the Legend into the Annunciator 

Cut the film to size, unclip the Omni8

 front-plate by pulling on the upper edge, and insert the 

film into the recess behind the front-plate. 

Replace the front-plate. 

Содержание Omni8m C1477B Series

Страница 1: ...Omni8 Alarm Annunciator C1477B x...

Страница 2: ...in any form or by any means electronically photocopying mechanical or otherwise nor its contents disclosed either wholly or in part without the consent in writing of or in accordance with the conditi...

Страница 3: ...m annunciator systems Available in a range of power supply options the rugged Omni8 is designed to fit directly into local electrical panels without the need for external power conditioning or interfa...

Страница 4: ...ATION 11 3 1 Installing the Omni8 in a panel 11 4 ELECTRICAL INSTALLATION 12 4 1 Introduction 12 4 2 Connection Table 12 4 3 Connecting the alarm inputs 12 4 4 Connecting the Relay 13 4 5 Connecting t...

Страница 5: ...nt monitoring Integral audible device and control pushbuttons for ease of installation and use Relay output for common group alarm or external audible device control Removable terminals for easy insta...

Страница 6: ...ction Figure 1 3 Side View showing 8 way Set up Switches 1 5 Installation and Set up Procedure The following steps should be implemented in the order shown to configure and install an Omni8 alarm annu...

Страница 7: ...witch of SW2 e g SW2 1 sets the contact sense for input 1 and SW2 8 sets the contact sense for input 8 When the switch is OFF up then the input is set to NORMALLY OPEN i e the input will enter the ala...

Страница 8: ...12 0 0 1 1 0 MOMENTARY ALARM AUTO RESET TIME DELAY ON RETURN TO NORMAL 16 60 seconds 13 1 0 1 1 0 PULSE MONITORING ALARM MANUAL RESET 17 17 1 1 1 1 0 INPUTS 1 4 SEQUENCE 1 INPUTS 5 8 SEQUENCE 27 FOR...

Страница 9: ...d normally by pressing the Silence or Acknowledge Pushbutton This is useful in environments where the local internal audible will not be heard 4 Relay acts in Multiple Reflash Mode The relay is normal...

Страница 10: ...C1477B User Manual UMC1477BR04 10 Copyright Omniflex...

Страница 11: ...CKNESS 8mm MAXIMUM PANEL 42 44 92 180 48 Location of DIP switches Mounting bracket Figure 3 1 Mounting an Omni8 3 1 Installing the Omni8 in a panel Remove the metal bracket from the unit by removing t...

Страница 12: ...wetting 10 Relay Change over Contact Normally Open Connection 11 Relay Change over Contact Common Connection 12 Relay Change over Contact Normally Closed Connection 13 No Connection 14 Earth 15 dc Pow...

Страница 13: ...ported by all operating systems There is also a README TXT file on this disk Run this first to see which version of program you must run to use the supplied templates 5 2 Creating the Legend Film To c...

Страница 14: ...sequence When the Omni8 is put into its test routine by depressing the TEST pushbutton any existing alarm states are remembered and the alarm annunciator will revert to its previous state when it ret...

Страница 15: ...this procedure of marching sequence followed by the brief blank display period will be repeated continuously until the ACKNOWLEDGE pushbutton is depressed or until an input changes state This marchin...

Страница 16: ...C selectable by DIP switch Max open cct voltage 15V dc between Common positive and all input terminals Max closed cct current 2 mA per input Max loop resistance to detect closed circuit 200 ohms Min...

Страница 17: ...haracters 2 5mm Fast Flash Rate 140 flashes per minute Slow Flash Rate 35 flashes per minute TEMPERATURE RANGE Operating Relative Humidity 0 C to 60 C 32 F to 140 F Up to 90 RH non condensing Storage...

Страница 18: ...nts IEC 61000 4 4 1995 2 kV DC power port 1 kV input output lines Supply Variations IEC 61000 4 7 1991 24 V dc 15 10 RoHS Compliance 2011 65 EU RoHS2 ORDERING INFORMATION C1477B 1 Omni8 with PSU 10 15...

Страница 19: ...P ON 1 2 3 4 5 6 7 8 ON SEQUENCE SWITCH SETTING STATE 1 LAMP OFF HORN OFF HORN OFF Sequence 2 Momentary Fleeting Alarm Manual Reset Timer option off STATE 4 STATE 3 RESET WHILE NORMAL ABNORMAL LAMP ON...

Страница 20: ...Only No Lock in Auto Reset Timer option off STATE 4 STATE 3 RETURN TO NORMAL ABNORMAL LAMP ON HORN OFF 1 2 3 4 5 6 7 8 ON SEQUENCE SWITCH SETTING STATE 2 STATE 1 LAMP OFF HORN OFF SIL ACK LAMP FAST FL...

Страница 21: ...RETURN TO NORMAL ABNORMAL ACK WHILE NORMAL Sequence 4 Momentary Fleeting Alarm Manual Reset with Ringback Timer Delay on inputs RESET ABNORMAL 1 2 3 4 5 6 7 8 ON SEQUENCE SWITCH SETTING STATE 1 STATE...

Страница 22: ...FAST FLASH HORN ON FIRST OUT ACTIVE LAMP ON FIRST OUT INACTIVE RESET WHILE NORMAL Sequence 5 Momentary Fleeting Alarm First Out Manual Reset Auto Reset on subsequent Alarms RETURN TO NORMAL ABNORMAL S...

Страница 23: ...TIVE FIRST OUT INACTIVE FIRST OUT INACTIVE HORN ON FIRST OUT ACTIVE LAMP ON FIRST OUT INACTIVE RESET WHILE NORMAL ACK ACK WHILE ABNORMAL LAMP SLOW FLASH FIRST OUT ACTIVE LAMP ON LAMP ON LAMP FAST FLAS...

Страница 24: ...et Re alarm after time out if still abnormal RESET WHILE NORMAL ABNORMAL LAMP ON 1 2 3 4 5 6 7 8 ON SEQUENCE SWITCH SETTING HORN OFF STATE 1 STATE 2 STATE 3 STATE 4 LAMP OFF HORN OFF LAMP FAST FLASH H...

Страница 25: ...TIMER RUNNING TIME OUT LAMP FAST FLASH HORN ON TIMER OFF SIL LAMP FAST FLASH HORN OFF TIMER OFF ACK HORN OFF TIMER OFF T ACK LAMP SLOW FLASH Sequence 12 Momentary Fleeting Alarm Auto Reset with Time D...

Страница 26: ...TIMER OFF TIMER OFF LAMP OFF HORN OFF TIMER OFF TIMER OFF ABNORMAL RETURN TO NORMAL ABNORMAL RETURN TO NORMAL TIME OUT TIME OUT ACK WHILE ABNORMAL SIL ACK WHILE NORMAL ACK WHILE ABNORMAL ACK WHILE NOR...

Страница 27: ...L LAMP ON Sequence 21 Momentary Fleeting Alarm First Out Multiple Groups Auto Reset RETURN TO NORMAL ABNORMAL SUBSEQUENT 1 2 3 4 5 6 7 8 ON SEQUENCE SWITCH SETTING STATE 1 STATE 2 LAMP OFF HORN OFF SI...

Страница 28: ...INACTIVE HORN ON FIRST OUT ACTIVE LAMP ON FIRST OUT INACTIVE RETURN TO NORMAL ACK WHILE NORMAL ACK WHILE NORMAL ACK WHILE ABNORMAL ACK WHILE NORMAL LAMP ON LAMP ON LAMP FAST FLASH LAMP FAST FLASH LAM...

Страница 29: ...larm after time out if still abnormal RETURN TO NORMAL ABNORMAL LAMP ON 1 2 3 4 5 6 7 8 ON SEQUENCE SWITCH SETTING HORN OFF STATE 1 STATE 2 STATE 3 STATE 4 LAMP OFF HORN OFF LAMP FAST FLASH HORN ON SI...

Страница 30: ...OFF ACK HORN OFF TIMER OFF T ACK WHILE ABNORMAL LAMP SLOW FLASH ACK WHILE NORMAL Sequence 29 Pulse Monitoring Alarm Auto Reset 1 2 3 4 5 6 7 8 ON SEQUENCE SWITCH SETTING STATE 1 STATE 2 LAMP OFF HORN...

Отзывы: