UMM124XBR04.pdf
DIT Number
Description
114
Raw Analogue Output for I/O Slot 1, Channel 5
115
Raw Analogue Output for I/O Slot 1, Channel 6
116
Raw Analogue Output for I/O Slot 1, Channel 7
117
Raw Analogue Output for I/O Slot 1, Channel 8
118
Raw Analogue Output for I/O Slot 1, Channel 9
119
Raw Analogue Output for I/O Slot 1, Channel 10
120
Raw Analogue Output for I/O Slot 1, Channel 11
121
Raw Analogue Output for I/O Slot 1, Channel 12
122
Raw Analogue Output for I/O Slot 1, Channel 13
123
Raw Analogue Output for I/O Slot 1, Channel 14
124
Raw Analogue Output for I/O Slot 1, Channel 15
125
Raw Analogue Output for I/O Slot 1, Channel 16
126 – 141
Raw Analogue Output Data for I/O Slot 2, Channels 1-16
142 – 157
Raw Analogue Output Data for I/O Slot 3, Channels 1-16
158 – 173
Raw Analogue Output Data for I/O Slot 4, Channels 1-16
174 – 189
Raw Analogue Output Data for I/O Slot 5, Channels 1-16
190 – 205
Raw Analogue Output Data for I/O Slot 6, Channels 1-16
206 – 221
Raw Analogue Output Data for I/O Slot 7, Channels 1-16
222 – 207
Raw Analogue Output Data for I/O Slot 8, Channels 1-16
238 – 253
Raw Analogue Output Data for I/O Slot 9, Channels 1-16
254 – 269
Raw Analogue Output Data for I/O Slot 10, Channels 1-16
270 – 285
Raw Analogue Output Data for I/O Slot 11, Channels 1-16
286 – 301
Raw Analogue Output Data for I/O Slot 12, Channels 1-16
302 – 317
Raw Analogue Output Data for I/O Slot 13, Channels 1-16
318 – 333
Raw Analogue Output Data for I/O Slot 14, Channels 1-16
334 – 349
Raw Analogue Output Data for I/O Slot 15, Channels 1-16
350 – 589
Raw Analogue Input Data Area
The Raw Analogue Input values of Maxiflex Analogue Input modules can be read
from this data area. Individual analogue input channels are referenced by I/O Slot
and Channel number for easy access. 16 Channels are allocated per I/O Slot. The
following formula may be used to read input channels:
Input DIT = 350 + (channel-1) + (I/O_Slot –1) * 16
Refer to Appendix 3 for the data formats available from Maxiflex Analogue Input
Modules.
NOTE: The Raw data for a given I/O Slot will clear to zero if there is no input
module installed in that I/O Slot.