Maxiflex T2 CPU User Manual
38
-© Omniflex
UMM124XBR04.pdf
DIT Number
Description
51
Scanned Module ID for I/O Slot 1
Every I/O and NIM module has a unique Module ID code that identifies it on the
Maxiflex Rack. The ID code of the I/O or NIM module for this slot is displayed in
this register.
52
Scanned Module ID for I/O Slot 2
53
Scanned Module ID for I/O Slot 3
54
Scanned Module ID for I/O Slot 4
55
Scanned Module ID for I/O Slot 5
56
Scanned Module ID for I/O Slot 6
57
Scanned Module ID for I/O Slot 7
58
Scanned Module ID for I/O Slot 8
59
Scanned Module ID for I/O Slot 9
60
Scanned Module ID for I/O Slot 10
61
Scanned Module ID for I/O Slot 11
62
Scanned Module ID for I/O Slot 12
63
Scanned Module ID for I/O Slot 13
64
Scanned Module ID for I/O Slot 14
65
Scanned Module ID for I/O Slot 15
66 – 67
RESERVED
68
Subscription Block Status Bits Subscriptions 1-16
69
Subscription Block Status Bits Subscriptions 17-32
70 – 78
Networking Information
Status Information for the available network ports on the CPU hardware.
70
Programming Port Inactivity
A seconds counter that is reset to zero every time there is active communications
on the Programming Port. If there is no valid communications, the counter is
incremented every second.
71
Serial Port Inactivity
A seconds counter that is reset to zero every time there is active communications
on the Serial Port. If there is no valid communications, the counter is incremented
every second.
72
Network Port Inactivity
A seconds counter that is reset to zero every time there is active communications
on the Network Port. If there is no valid communications, the counter is
incremented every second.
73
Programming Port ID
This is the ID setting of the Programming Port – fixed at 65400
74
Serial Port Local ID
The local ID setting for the Serial Port as set on the Serial Port dipswitch, swtiches
1 to 6.
75
Serial Port Global ID
Содержание M124xA