CPC 100 V1.41
6 - 26
Voltage Withstand Test
Use the test card
VWithstand
to measure the voltage withstand capability of the
secondary winding and secondary wiring.
As shown in Figure 16, connect the 2kV output socket without point to the
transformer’s secondary (a) winding connection, and the output socket marked
with a point to earth and the transformer’s primary connection (A).
Warning
: Be aware that all the terminals of the transformer’s secondary side
carry life-hazardous voltage!
Figure 16:
Setup for a power
transformer voltage
withstand test
Note:
Some test cards are available in more than one test mode. For
example, the test card
VWithstand
can be selected in CT, VT,
Resistance and Transformer.
This is solely related to usability. With regard to functionality, the test
card
VWithstand
is identical in all test modes.