2
BAD
position.
Will not work properly!
BEST
position.
Recommended!
Possible
if no alternative position is
available. Not recommended!
Possible
position.
Mount
in an upright position
OTMC 100
with the protective cap to the top only!
Provide a suitable surge
protection device to the Ethernet
cable leading into the building!
Always observe all relevant
lightning protection regulations!
Use shielded Ethernet cable only!
4
1
3
1
Recommended mounting position with best possible reception of GPS signals.
This mounting position provides direct view to the sky. The view is not hindered by any
objects and the GPS signals are not influenced by any reflections.
2
Possible mounting position providing sufficient reception of GPS signals under most
conditions. This mounting position provides direct view to the sky in a range of nearly 180°.
The view is only partly hindered and there is negligible danger of reflections that could
influence the GPS signals.
3
Possible mounting position if no other mounting position is available. Not recommended!
This mounting position provides direct view to the sky for a range of more than 90° but much
less than 180°. The view to the right is hindered by the taller part of the building and there is
an increased danger of reflections that could influence the GPS signals.
4
Bad mounting position. Do not use!
This mounting position provides direct view to the sky for a range of only 90°. Half the sky is
blocked by the taller part of the building and the reception of GPS signals will be considerably
influenced by reflections.
OTMC 100
will not work properly.