![background image](http://html1.mh-extra.com/html/omega/wm-09k/wm-09k_service-manual_3968636050.webp)
Air Conditioner Service Manual
42
3. If the unit can’t operate, please replace outdoor PCB
11.3.11 Display EC
Reason:
The signal communication fault between power module and IPM module.
Solution:
Please replace the outdoor PCB.
11.3.12 Display EP
Reason:
The compressor top temperature high or the sensor fault.
Solution:
Check and replace the sensor or add some gas.
11.3.13 Display PA
Reason:
Two or three machine modes collide.
Solution:
Check whether one machine run in cooling another machine run in heating or other model.
11.3.14 Display D3.
Reason:
Water full (This only apply to cassette or duct type).
Solution:
Check and let water drain.
11.13.15
Display CL
Cause:
Air filter duty, the unit operation Cumulative time 500 hours, the controller will confirmation the filter
dirty and display CL.
Solution: Clean the air filter then cut off the power and supply again.
Содержание WM 09K
Страница 15: ...Air Conditioner Service Manual 14 6 Wiring diagram INDOOR UNIT Wall split type Cassette Duct type ...
Страница 16: ...Air Conditioner Service Manual 15 OUTDOOR UNIT ONE TO 2 TYPE ONETO 3TYPE ...
Страница 17: ...Air Conditioner Service Manual 16 ONE TO 4 TYPE ...
Страница 23: ...Air Conditioner Service Manual 22 CASSETTE TYPE INDOOR UNIT ...