Air Conditioner Service Manual
44
11.4.2 DC Over Current Error
Error memory is
recorded
Start
Are valves (2-way
or 3-war) close?
Full open stop valves
Does compressor
rotates?
Does compressor
rotates more than
30 seconds?
Check IPM lead
wire (UVW)
Is
IPM PWB
floating
from the heat sink
?
Fix
IPM PWB
with screws
securely.
Check
the AC power
supply voltage when
compressor rotate.(rated
voltage±10%)
Check
IPM
short
circuit
.
Modify the connection of
compressor lead wire on
PWB
Replace
PWB
.
Cooling mode?
.
Check
compressor
Modify compressor terminal
marking
Replace PWB
Does compressor
rotates?
Replace
compressor
Check indoor
exchange sensor
and discharge
sensor
Modify or replace
the sensor
.
Check outdoor
exchange sensor
and discharge
sensor
Modify or replace
the sensor
.
Check indoor
heat exchange
.
Check outdoor
heat exchange
Clean indoor heat
exchange
Clean outdoor
heat exchange
Check the refrigerant
amount
Check the discharge
press
Check the installation
condition
Yes
Yes
No
No
No
No
Yes
Yes
Abnormal
Abnormal
Abnormal
Normal
Normal
Normal
Normal
Normal
Normal
No
Yes
Abnormal
Abnormal
Abnormal
Abnormal
Normal
Содержание WM 09K
Страница 15: ...Air Conditioner Service Manual 14 6 Wiring diagram INDOOR UNIT Wall split type Cassette Duct type ...
Страница 16: ...Air Conditioner Service Manual 15 OUTDOOR UNIT ONE TO 2 TYPE ONETO 3TYPE ...
Страница 17: ...Air Conditioner Service Manual 16 ONE TO 4 TYPE ...
Страница 23: ...Air Conditioner Service Manual 22 CASSETTE TYPE INDOOR UNIT ...