The voltage on the Analog Output pin on the REC2 will correspond to the
value of this sensor.
Timeout:
This setting is to indicate the number of seconds you want the REC2 to wait
before displaying a NO SIGNAL message on the display.
Process Units:
Choose the units which will be used to set the limits of the analog output
scaling.
Custom Units:
A custom unit type can be entered here.
Alarm Activation Mode:
This will set the alarm to activate on the rising or falling temperature when
your setpoint is reached.
Alarm Setpoint:
Set the setpoint (in degrees F) that you want the alarm to activate at.
Alarm Deadband:
The number of units away from the Alarm Setpoint before the alarm will be
activated again.
Decimal Places:
Number of decimal places in the Alarm Setpoint and Alarm Deadband values.
SCALING:
Enter one value, in Process Units, that will set the analog output to its
minimum value (such as 0 V) and another value, in Process Units, that will set
the analog output to its maximum value (such as 10 V).
UWTC-REC4:
The configuration window for the UWTC-REC4 features a tabbed interface
that allows the user to configure all of the relevant settings described for the
UWTC-REC2 for each of the four analog output channels.
5.1.2 Setting Values:
To set these values, launch TC Central (Start | Programs | TC Central) and
then select Configure Receiver from the Tools menu. The following figures
show what the configuration screen will look like, based on the version of your
receiver:
Receiver Operation
5
5-9