background image

57

Installation and Maintenance

Service Manual

Possible Causes 

Discriminating Method (Air conditioner Status)

Troubleshooting 

Set temperature is improper

Observe the set temperature on remote controller  Adjust the set temperature

Rotation speed of the IDU fan 

motor is set too low

Small wind blow 

Set the fan speed at high or medium 

Filter of indoor unit is blocked 

Installation position for indoor unit 
and outdoor unit is improper 

Check whether the installation postion is proper 

according to installation requirement for air 
conditioner 

Adjust the installation position, and install the 

rainproof and sunproof for outdoor unit

Refrigerant is leaking 

Discharged air temperature during cooling is 

Discharged air temperature during heating is 

Units pressure is much lower than regulated 

range 

Find out the leakage causes and deal with it. 

Add refrigerant. 

Malfunction of 4-way valve 

Blow cold wind during heating 

Replace the 4-way valve 

Malfunction of capillary

Discharged air temperature during cooling is 

Discharged air temperature during heating is 

Unitt pressure is much lower than regulated 

range. If refrigerant isnt leaking, part of capillary 
is blocked 

Replace the capillary

Flow volume of valve is 

The pressure of valves is much lower than that 

Open the valve completely 

Malfunction of horizontal louver  Horizontal louver Can't swing 

Refer to point 3 of maintenance method for 

details 

Malfunction of the IDU fan motor  The IDU fan motor Can't operate 

Refer to troubleshooting for H6 for maintenance 
method in details 

Malfunction of the ODU fan motor The ODU fan motor Can't operate 

Refer to point 4 of maintenance method for 

details 

Malfunction of compressor 

Compressor Can't operate 

Refer to point 5 of maintenance method for 

details 

.3 Troubleshooting for Normal Malfunction

1. Air Conditioner Can't be Started Up

2. Poor Cooling (Heating) for Air Conditioner

3. Horizontal Louver Can't Swing

Possible Causes 

Discriminating Method (Air conditioner Status)

Troubleshooting 

No power supply, or poor 

connection for power plug

After energization, operation indicator isnt bright 

and the buzzer Can't give out sound 

wait for power recovery. If not, check power 

supply circuit and make sure the power plug is 

connected well. 

Wrong wire connection between 
indoor unit and outdoor unit, 

or poor connection for wiring 

terminals 

Under normal power supply circumstances, 

operation indicator isnt bright after energization

Check the circuit according to circuit diagram 

and connect wires correctly. Make sure all 

Electric leakage for air conditioner After energization, room circuit breaker trips off at 

once

Make sure the air conditioner is grounded 
reliably

Make sure wires of air conditioner is connected 

correctly

Check the wiring inside air conditioner. Check 
whether the insulation layer of power cord is 

Model  selection  for  air  switch  is 

improper

After energization, air switch trips off

Select proper air switch

Malfunction of remote controller 

After energization, operation indicator is bright, 
while no display on remote controller or buttons 

have no action. 

Replace batteries for remote controller
Repair or replace remote controller

Possible Causes 

Discriminating Method (Air conditioner Status)

Troubleshooting 

Wrong wire connection, or poor 

connection 

Check the wiring status according to circuit 

diagram 

Connect wires according to wiring diagram to 

make sure all wiring terminals are connected 

Stepping motor is damaged 

Stepping motor Can't operate 

Repair or replace stepping motor 

Main board is damaged 

Others are all normal, while horizontal louver 

Can't operate 

Replace the main board with the same model

Содержание OTEC IEWQ Series

Страница 1: ......

Страница 2: ...l Information 1 1 Summary 1 Removal Procedure 1 Removal Procedure of Indoor Unit 2 Removal Procedure of Outdoor Unit Troubleshooting 1 Flashing LED of Indoor Outdoor Unit and Primary Judgement 2 Proce...

Страница 3: ...1 Technical Information Service Manual 1 Summary Part Technical Information Indoor Unit Outdoor Unit Remote Controller...

Страница 4: ...35 Installation and Maintenance Service Manual Troubleshooting 1 Flashing LED of Indoor Outdoor Unit and Primary Judgement...

Страница 5: ...36 Installation and Maintenance Service Manual...

Страница 6: ...37 Installation and Maintenance Service Manual...

Страница 7: ...38 Installation and Maintenance Service Manual...

Страница 8: ...39 Installation and Maintenance Service Manual...

Страница 9: ...ion for evaporator E2 Not the error code It s the status code for the operation 50 Cold air prevention protection E9 Not the error code It s the status code for the operation 51 Refrigerant recovery m...

Страница 10: ...n indoor unit and detection 53 Defrosting Heating indicator off for 0 5s and then blinks for 10s Not the error code It s the status code for the operation 54 outdoor unit error oE Cool compressor and...

Страница 11: ...n the controller and if damage of lead wire is found 5 Compressor over load protection 6 System malfun ction Overload protection When tube temperature Check the temperature of outdoor heat exchanger w...

Страница 12: ...he temperature sensor and the controller Start Insert the temperature sensor tightly Yes Yes Yes Yes Yes Yes No No No No No No Is malfunction eliminated Is malfunction eliminated Is malfunction elimin...

Страница 13: ...44 Installation and Maintenance Service Manual 2 Malfunction of Blocked Protection of IDU Fan Motor H6...

Страница 14: ...art Is the jumper cap inserted correctly Replace the jumper cap with the same model Appearance of the jumper cap Assemble the jumper cap with the same model Insert the jumper cap tightly Is malfunctio...

Страница 15: ...46 Installation and Maintenance Service Manual 4 Malfunction of detecting plate WIFI JF...

Страница 16: ...47 Installation and Maintenance Service Manual 5 Communication malfunction E6...

Страница 17: ...48 Installation and Maintenance Service Manual Outdoot Unit...

Страница 18: ...49 Installation and Maintenance Service Manual 2 IPM protection phase current overcurrent the control board as below indicates the control board of outdoor unit H5 P5...

Страница 19: ...50 Installation and Maintenance Service Manual...

Страница 20: ...51 Installation and Maintenance Service Manual...

Страница 21: ...52 Installation and Maintenance Service Manual...

Страница 22: ...53 Installation and Maintenance Service Manual...

Страница 23: ...54 Installation and Maintenance Service Manual...

Страница 24: ...55 Installation and Maintenance Service Manual...

Страница 25: ...56 Installation and Maintenance Service Manual 9 High pressure Protection...

Страница 26: ...point 5 of maintenance method for details 3 Troubleshooting for Normal Malfunction 1 Air Conditioner Can t be Started Up 2 Poor Cooling Heating for Air Conditioner 3 Horizontal Louver Can t Swing Poss...

Страница 27: ...n pipe is broken Water leaking from drain pipe Replace drain pipe Wrapping is not tight Water leaking from the pipe connection place of indoor unit Wrap it again and bundle it tightly 5 Compressor Can...

Страница 28: ...63 Installation and Maintenance Service Manual Removal Procedure Caution discharge the refrigerant completely before removal 1 Removal Procedure of Indoor Unit...

Страница 29: ...64 Installation and Maintenance Service Manual...

Страница 30: ...65 Installation and Maintenance Service Manual...

Страница 31: ...66 Installation and Maintenance Service Manual...

Страница 32: ...67 Installation and Maintenance Service Manual...

Страница 33: ...68 Installation and Maintenance Service Manual...

Страница 34: ...69 Installation and Maintenance Service Manual...

Страница 35: ...70 Installation and Maintenance Service Manual...

Страница 36: ...71 Installation and Maintenance Service Manual...

Страница 37: ...72 Installation and Maintenance Service Manual 2 Removal Procedure of Outdoor Unit...

Страница 38: ...73 Installation and Maintenance Service Manual...

Страница 39: ...74 Installation and Maintenance Service Manual...

Страница 40: ...75 Installation and Maintenance Service Manual...

Страница 41: ...76 Installation and Maintenance Service Manual...

Страница 42: ...15 82 83 82 4 28 37 38 37 4 3 61 62 60 8 16 84 85 84 2 29 39 40 39 2 4 63 62 6 17 86 87 86 30 41 42 41 5 64 65 64 4 18 88 89 87 8 31 43 44 42 8 6 66 67 66 2 19 90 89 6 32 45 44 6 7 68 69 68 20 91 92 9...

Страница 43: ...main cause of refrigerant leakage Please expand the pipe according to the following steps A Cut the pip B Remove the burrs C Put on suitable insulating pipe D Put on the union nut the union nut on th...

Страница 44: ...0 737 5 63 46 34 10 2 73 2 358 112 0 717 4 60 23 35 9 779 74 2 28 113 0 697 3 57 18 36 9 382 75 2 206 114 0 678 2 54 31 37 9 003 76 2 133 115 0 66 1 51 59 38 8 642 77 2 064 116 0 642 0 49 02 39 8 297...

Страница 45: ...144 112 0 956 4 80 31 35 13 04 74 3 04 113 0 93 3 76 24 36 12 51 75 2 94 114 0 904 2 72 41 37 12 76 2 844 115 0 88 1 68 79 38 11 52 77 2 752 116 0 856 0 65 37 39 11 06 78 2 663 117 0 833 1 62 13 40 10...

Страница 46: ...24 51 41 63 10 93 102 3 13 14 342 8 25 49 19 64 10 54 103 3 04 13 323 9 26 47 08 65 10 18 104 2 96 12 306 2 27 45 07 66 9 83 105 2 87 11 289 6 28 43 16 67 9 49 106 2 79 10 274 29 41 34 68 9 17 107 2...

Страница 47: ......

Отзывы: