background image

 

 

Test And Adjusting Gas Pressure 

NATURAL GAS –  

Appliance test point located at the regulator

 

The supplied regulator must be fitted to the appliance inlet connection. Gas pressure must be adjusted to 

1.0 kPa when approximately 50% of the burners are on a high setting. 

 

UNIVERSAL LPG –  

Appliance test point located at the burner injector

 

Gas pressure must be checked to confirm the appliance operating pressure is 2.75 kPa, the appliance test 

point is the rapid burner injector as shown below. 

1.  Disconnect power 

2.  Manually light the auxiliary burner and set to high flame 

3.  Zero manometer, then apply flexible tubing to seal over the rapid burner injector, hold securely in 

place and check the gas pressure by pressing in the corresponding burner control knob on high 

flame position. 

4.  If the pressure is 2.75 kPa, reassemble the burner and perform the final checks as per this 

instruction manual. 

5.  If the pressure is 

not

 2.75 kPa, disconnect the appliance and check/adjust/replace the LPG cylinder 

regulator(s) in accordance with AS/NZS 5601. 

 

If the appliance is supplied with an LPG test point adaptor, then this component may be fitted to the 

inlet connection for the purpose of a test point. 

 

Содержание OCG905X

Страница 1: ...Instruction Manual Gas Cooktop OCG95XTGG OCG95FFETGG OCG95XCOM OCG95FFECOM OCG905X...

Страница 2: ...iance such as warranty registration manuals features and specifications please visit omegaappliances com au if you are in Australia and omegaappliances co nz if you are in New Zealand or contact our C...

Страница 3: ...and appearances without notice Contents Important Safety Warnings 4 Appliance Details 5 Gas Connections 6 Test And Adjusting Gas Pressure 8 Electrical Connections 9 Operating Instructions 11 Cleaning...

Страница 4: ...t be replaced by the manufacturer it s service agent or similarly qualified persons in order to prevent a hazard 7 The electrical and gas connections must be accessible after installation 8 Electrical...

Страница 5: ...t face e g 1 8 for 1 80mm injector Table of recommended pot sizes for each burner type Control Knob functions are displayed around each knob as shown below Relevant Sizes LENGTH mm WIDTH mm HEIGHT mm...

Страница 6: ...rom front 30mm in from the back edge The fitting fig 2 is made up of 1 elbow fitting A 1 gaskets F The hob must be installed in a room with adequate ventilation see installation section N G Fit the su...

Страница 7: ...d On gas valves provided with adjustment screw on the valve body fig 22 Turn the screw A to the correct setting with a screwdriver LUBRICATION OF THE GAS TAPS This can only be performed by an authoris...

Страница 8: ...connect power 2 Manually light the auxiliary burner and set to high flame 3 Zero manometer then apply flexible tubing to seal over the rapid burner injector hold securely in place and check the gas pr...

Страница 9: ...or coloured red After having installed the appliance the power switch or power plug must always be in an accessible position Electrical connection diagram N B For connections to the mains power suppl...

Страница 10: ...g fan underneath the hob is forbidden PREPARING PLACING THE HOB FOR INSTALLATION Every cooker top is provided with a set of tabs for fitting to the unit with thickness from 3 to 4 cm and a seal with a...

Страница 11: ...are placed correctly on the burner rings USING THE BURNERS For greater efficiency and less gas consumption use pots and pans with the right diameters for the burners Avoid having flames extending out...

Страница 12: ...d before use Ensure that all components are placed back onto the cooktop correctly Failure to do so can cause problems with the burners igniting and functioning correctly See diagrams on the following...

Страница 13: ...ents Burner not assembled correctly Refer to assembly instruction manual Burner ignites but flame goes out when control knobs released Control knob not depressed down enough when igniting burner contr...

Страница 14: ...14 Notes Service History...

Страница 15: ...st of service or repair Service Area The provision of service under Our Warranty is limited by the boundary territory area of the nearest service centre Travelling cost incurred for service outside th...

Страница 16: ...1 IM Rev1 6...

Отзывы: