10
Table 3-1. Calibration Values
Temperature
mV Input
mV Input
Input Range Model
Ref 32°F
Model
Ref 32°F
Zero/Span
TX93A Zero/Span
TX93A
Zero/Span
-40/120°F -J1
-1.961/2.527
-
-
0/200°F
-J2 -0.886/4.907
-K2 -0.692/3.820
0/300°F -J3 -0.886/7.949
-K3 -0.692/6.094
0/500°F -J4 -0.886/14.110
-K4 -0.692/10.561
0/750°F -J5 -0.886/21.787
-K5 -0.692/16.350
0/1000°F -J6 -0.886/29.521
-K6
-0.692/22.255
-40/120°F –
–
-E1
-2.255/2.977
0/200°F -T2 -0.675/3.968
-E2
-1.026/5.871
0/300°F -T3 -0.675/6.648
-E3
-1.026/9.710
0/500°F -T4 -0.675/12.574
-E4 -1.026/17.945
0/750°F -T5 -0.675/20.803
-E5 -1.026/28.857
0/1000°F –
–
-E6 -1.026/40.064
4.1 Troubleshooting Guide
Malfunction or incorrect operation may be caused by:
1.
Reversed polarity:
Check the wiring using
Figure 2-2
as a guide. If the temperature
of the thermocouple increases while the current magnitude
decreases, the problem could be caused by reversed polarity of
the:
a)
thermocouple wiring
b)
power supply leads
c)
monitor instrument