Command Formats
cont.
No spaces are allowed in the data string. The spaces provided in the previous example are for illustration purposes only.
Decimal Point position for TC/RTD = 1 or 2, for PROCESS = 1, 2 , 3, or 4.
Decimal Point position for setpoint should be the same as Decimal Point position sets for Process Value and can not be
overwritten by SETPOINT command. (See RDGCNG command, described below.)
4.
To change Setpoint 1 to -100.0
For (-100.0): Negative sign = 1, Decimal Point 2 = 010 Bin, Setpoint data 1000 = 3E8 Hex = 001111101000 Bin
The command data =
1010
0000
0000
0011
1110
1000 Bin = A003E8 Hex
A
0
0
3
E
8
Send *W01A003E8
5.
To send the same as above for RS-485 of transit address 01 the command is *01W01A03E8.
Default settings are Recog. Char. Ò*Ó, 9600 bps, 7 data, 1 stop, and Odd Parity.
Note
☞
Note
☞
Note
☞
Note
☞
Содержание MICROMEGA CN77000 series
Страница 4: ...NOTES ...
Страница 19: ...SETUP part 2 11 Dip Switch Settings ...
Страница 31: ...Figure 3 2 Flowchart for Input Type OPERATION CONFIGURATION MODE part 3 23 ...
Страница 36: ...Figure 3 3 Flowchart for Reading Configuration part 3 OPERATION CONFIGURATION MODE 28 ...
Страница 45: ...Figure 3 5 Flowchart for Loop Break OPERATION CONFIGURATION MODE part 3 37 ...
Страница 49: ...OPERATION CONFIGURATION MODE part 3 41 Figure 3 6 Flowchart for Output 1 ...
Страница 59: ...OPERATION CONFIGURATION MODE part 3 51 Figure 3 7 Flowchart for Output 2 ...
Страница 65: ...OPERATION CONFIGURATION MODE part 3 57 Figure 3 8 Flowchart for Ramp Soak ...
Страница 69: ...OPERATION CONFIGURATION MODE part 3 61 Analog Output Option Figure 3 9 Flowchart for Analog Output Option ...
Страница 72: ...part 3 OPERATION CONFIGURATION MODE Communication Option Figure 3 10 Flowchart for Communication Option 64 ...
Страница 96: ...part 3 OPERATION CONFIGURATION MODE 88 Remote Setpoint Option Figure 3 11 Flowchart for Remote Setpoint ...