O
PERATION
:
C
ONFIGURATION
M
ODE
part
3
55
Output 2
cont.
Display
Action
Response
CYCLE TIME SUBMENU:
Press ENTER
15) Display flashes 1st digit of the previous
"
Cycle Time
"
value.
Press MAX & MIN
16) Press MAX and MIN buttons to enter a new
"
Cycle Time
"
value. (1 to 199 seconds).
Press ENTER
17) Display flashes
"
stored
"
message and advances to
"
Ramp & Soak
"
Menu.
A Cycle Time selected between 1 to 199 seconds indicates the total On/Off time of each proportional cycle. For example, a
15 second Cycle Time means that every 15 seconds the output will turn on for part or all of the cycle. For Relay control
outputs, do not select a cycle time of less than 7 seconds or the relays life time will be shortened. For a cycle time of less
than 7 seconds select SSR or DC pulse. Use an external SSR with the DC pulse option for higher current (higher than 1 Amp).
C
Y
C
L
0010
C
Y
C
L
TIME
Note
☞
Содержание MICROMEGA CN77000 series
Страница 4: ...NOTES ...
Страница 19: ...SETUP part 2 11 Dip Switch Settings ...
Страница 31: ...Figure 3 2 Flowchart for Input Type OPERATION CONFIGURATION MODE part 3 23 ...
Страница 36: ...Figure 3 3 Flowchart for Reading Configuration part 3 OPERATION CONFIGURATION MODE 28 ...
Страница 45: ...Figure 3 5 Flowchart for Loop Break OPERATION CONFIGURATION MODE part 3 37 ...
Страница 49: ...OPERATION CONFIGURATION MODE part 3 41 Figure 3 6 Flowchart for Output 1 ...
Страница 59: ...OPERATION CONFIGURATION MODE part 3 51 Figure 3 7 Flowchart for Output 2 ...
Страница 65: ...OPERATION CONFIGURATION MODE part 3 57 Figure 3 8 Flowchart for Ramp Soak ...
Страница 69: ...OPERATION CONFIGURATION MODE part 3 61 Analog Output Option Figure 3 9 Flowchart for Analog Output Option ...
Страница 72: ...part 3 OPERATION CONFIGURATION MODE Communication Option Figure 3 10 Flowchart for Communication Option 64 ...
Страница 96: ...part 3 OPERATION CONFIGURATION MODE 88 Remote Setpoint Option Figure 3 11 Flowchart for Remote Setpoint ...