FTB700 SERIES INSTRUCTIONS

 

Page 4 

omega.com

This  unique  system  of  3"  to  8"  turbine  meters  uses  just  one 
moving  part,  a  precision  helical  rotor.    Rotation  of  the  rotor  is 
electronically  detected  and  processed.    The  high-quality  jewel 
bearings  and  shafts  minimize  friction  while  providing  long  life 
in non-lubricating fluids. The entire rotor assembly can be easily 
removed for field service without removing the meter from the 

pipe. 

FTB700 bodies are fabricated from Schedule 80 PVC fittings or 
from  stainless  steel  tubing.  The  turbine  insert  on  the  stainless 
steel meters is machined from a stainless steel casting. The PVC 
turbine  insert  is  machined  from  a  solid  piece  of  PVC.  Turbine 
rotors on all models are PVDF.

FTB700 meters can be ordered with various output options. The 
basic model comes with pulse output only. An electronic display 
is available on the DPF144-P/DPF144-W model to display flow 
rate  and  total  (resettable  or  non-resettable),  and  provide  a 
programmable pulse or 4-20 mA output. The controls/displays 
can be mounted on the meter or remotely mounted on a wall 
or panel up to 2,000 feet away. FTB700 meters are compatible 
for use with other remote-mount Omega displays and controls 
as well.

GENERAL INFORMATION

Specifications*

Electronic Options Specifications*

FTB700

FTB700

DPF144-P/DPF144-W

Power

6-36 Vdc

7-30 Vdc

7-30 Vdc, 4mA

(4-20 mA when loop powered)

Electronic Display

DPF143

DPF144

Pulse Out

0-160 pulse/sec. current sinking

Pulse scaled and pulse pass through

Pulse scaled

Analog Out

4-20 mA Loop

Rate

5-digit autorange

5-digit autorange

Total

8-digit

8-digit

Memory

Non-volatile

Non-volatile

Response Time
High/Low Alarm

Selectable on one output

Selectable on one output

Regulatory 

 Mark  

 Mark  

 Mark   

PVC

Stainless Steel

Pipe Sizes

3”, 4”, 6”

3”, 4”, 6”, 8”

Materials Meter Body

PVC Schedule 80 fittings

304 Stainless steel (316 SS optional)

Turbine Insert

PVC

CF8 cast stainless

Rotor

PVDF

PVDF

Shaft

Zirconia ceramic

Zirconia ceramic

Bearings

Sapphire journal, ruby endstone

Sapphire journal, ruby endstone

Cable

#22 AWG, 2000’ max

#22 AWG, 2000’ max

Flanges

Optional (See dimensions)

150 lb. drilling

Maximum Pressure

150 psi @ 75° F)

(10 bar @ 24° C) (See chart)

200 psi (14 bar)

Maximum Temperature

120° F (50° C) (See chart)

200° F (93° C)

Accuracy

± 1% of full scale

± 1% of full scale

Flow Range (GPM)

3”

4”

6”

3”

4”

6”

8”

Minimum

3

6

12

3

6

12

30

Maximum

400

600

1200

400

600

1200

3000

* Specifications subject to change. Please consult our web site for current data (omega.com).

Содержание FTB700

Страница 1: ...e mail info omega com For latest product manuals www omegamanual info User sGuide Shop online at omega comSM PVC Stainless Steel FTB700 SERIES Inline Turbine Meters ...

Страница 2: ...eering Service 1 800 872 9436 USA Canada only Tel 203 359 1660 Fax 203 359 7700 e mail info omega com For Other Locations Visit omega com worldwide omega com info omega com The information contained in this document is believed to be correct but OMEGA accepts no liability for any errors it contains and reserves the right to alter specifications without notice ...

Страница 3: ...pair Installation Page 5 Connections Page 5 Maintenance and Repair Page 5 Replacement Parts Page 6 FTB700 T BLIND ANALOG TRANSMITTER General Information General Information Page 7 Specifications Page 7 Features Page 8 Installation Installation Page 8 Connections Page 8 Settings and Calibration Setting Frequency Page 9 Setting Averaging Time Page 9 Checking Calibration Page 9 Troubleshooting Proble...

Страница 4: ...e compatible for use with other remote mount Omega displays and controls as well GENERAL INFORMATION Specifications Electronic Options Specifications FTB700 FTB700 DPF144 P DPF144 W Power 6 36 Vdc 7 30 Vdc 7 30 Vdc 4mA 4 20 mA when loop powered Electronic Display DPF143 DPF144 Pulse Out 0 160 pulse sec current sinking Pulse scaled and pulse pass through Pulse scaled Analog Out 4 20 mA Loop Rate 5 ...

Страница 5: ...EPAIR PVC Meter Stainless Steel Meter Maintenance and Repair Recalibration If it is necessary to recalibrate the meter for any reason please contact Omega Turbine Insert Removal and Installation CAUTION First remove all pressure from the line Then remove the screws or bolts that hold the insert in place and tug gently until the insert comes free A twisting motion can help to loosen the O ring seal...

Страница 6: ...298 100298 10 Pickup 100419 100419 11a Insert SS N A 100440 11b Insert 3 PVC 100438 N A 11c Insert 4 6 PVC 100439 N A 12 Shaft assembly ceramic includes 2 103312 103312 13 Rotor PVDF bearing assembly 100333 100333 14 O ring EPDM 100214 100270 15 Insert screw 4 req d 100023 N A ALL METERS White Housing Blue Housing 1 Upper housing electronics Contact service representative for your specific model C...

Страница 7: ...g is cast from aluminum and fuse coated The clamshell housing is provided with mounting feet or remote mounting The FTB700 T will operate on a relatively wide range of current loop voltages 24 to 36 Vdc Lower voltages limit the load that can be applied to the loop without distortion of the signal See Load Supply chart if there is a question regarding voltage vs load A built in power regulator supp...

Страница 8: ...terminal blocks in the upper half which contains the potted electronics Installation Connections 0 9 8 7 6 5 4 3 2 1 0 9 8 7 6 5 4 3 2 1 0 9 8 7 6 5 4 3 2 1 0 9 8 7 6 5 4 3 2 1 Frequency Power Sensor 4 20 mA 4 20 mA Device e g Pump PLC Chart Recorder 24 36 Vdc Power Supply may be included in control unit Red White Black S FTB700 Series FTB700 T 4mA Adjust Force 4 mA Force 20 mA 20 mA Adjust FTB700...

Страница 9: ...d their corresponding times Checking Calibration Normally it should not be necessary to check calibration since the digital design of this unit virtually eliminates drift However there are two types of calibration check that can be performed Look at the diagram below to locate the 4 and 20 mA force switches To force the 4 mA output put its switch in the up position Check the current output at the ...

Страница 10: ...ty Check polarity Output stick at 4 mA No frequency input from flow sensor Check flow sensor connections Check flow sensor polarity Be sure terminal blocks are firmly plugged in With flow sensor disconnected use short wire to repeatedly short between sensor S and terminals Output should rise mA signal does not match flow rate Inadequate voltage Check load vs supply chart Wrong frequency setting Re...

Страница 11: ...by OMEGA if the unit is found to be defective it will be repaired or replaced at no charge OMEGA s WARRANTY does not apply to defects resulting from any action of the purchaser including but not limited to mishandling improper interfacing operation outside of design limits improper repair or unauthorized modification This WARRANTY is VOID if the unit shows evidence of having been tampered with or ...

Страница 12: ...elocity Indicators M U Turbine Paddlewheel Systems M U Totalizers Batch Controllers pH CONDUCTIVITY M U pH Electrodes Testers Accessories M U Benchtop Laboratory Meters M U Controllers Calibrators Simulators Pumps M U Industrial pH Conductivity Equipment DATA ACQUISITION M U Communications Based Acquisition Systems M U Data Logging Systems M U Wireless Sensors Transmitters Receivers M U Signal Con...