Modbus Register Assignments 

7

Index

Mnemonic

Type Access

Description

0x0100

40256

Temperature Zone 1

F

R

Zone 1 Process Value

0x0102

40258

Temperature Zone 2

F

R

Zone 2 Process Value

0x0104

40260

Temperature Zone 3

F

R

Zone 3 Process Value

0x0106

40262

Temperature Zone 4

F

R

Zone 4 Process Value

0x0108

40264

Temperature Zone 5

F

R

Zone 5 Process Value

0x010a

40266

Temperature Zone 6

F

R

Zone 6 Process Value

0x010c

40268

Temperature Zone 7

F

R

Zone 7 Process Value

0x010e

40270

Temperature Zone 8

F

R

Zone 8 Process Value

0x0110

40272

Temperature Zone 9

F

R

Zone 9 Process Value

0x0112

40274

Temperature Zone 10

F

R

Zone 10 Process Value

0x0114

40276

Temperature Zone 11

F

R

Zone 11 Process Value

0x0116

40278

Temperature Zone 12

F

R

Zone 12 Process Value

Section 7.2 - Temperature Registers

Index

Mnemonic

Type Access

Description

0x0180

40384

Sensor Status Zone 1

R

R

Zone 1 Sensor status

0x0181

40385

Sensor Status Zone 2

R

R

Zone 2 Sensor status

0x0182

40386

Sensor Status Zone 3

R

R

Zone 3 Sensor status

0x0183

40387

Sensor Status Zone 4

R

R

Zone 4 Sensor status

0x0184

40388

Sensor Status Zone 5

R

R

Zone 5 Sensor status

0x0185

40389

Sensor Status Zone 6

R

R

Zone 6 Sensor status

0x0186

40390

Sensor Status Zone 7

R

R

Zone 7 Sensor status

0x0187

40391

Sensor Status Zone 8

R

R

Zone 8 Sensor status

0x0188

40392

Sensor Status Zone 9

R

R

Zone 9 Sensor status

0x0189

40393

Sensor Status Zone 10

R

R

Zone 10 Sensor status

0x018a

40394

Sensor Status Zone 11

R

R

Zone 11 Sensor status

0x018b

40395

Sensor Status Zone 12

R

R

Zone 12 Sensor status

0x018c

40396

Sensor Status Bitmap

R

R

Sensor status bitmap for all zones

0x018d

40397

Alarm Status Bitmap

R

R

Alarm status bitmap for all zones

Section 7.3 - Status Registers

Table 12 - Temperature Registers

Table 13 - Sensor Status Registers

24

Содержание DP606A

Страница 1: ...e mail info omega com For latest product manuals www omegamanual info DP606A DP612A Universal 6 12 Channel DIN Panel Meter TM Shop online at omega com User sGuide...

Страница 2: ...ce omega com info omega com Servicing North America Omega Engineering Inc 800 Connecticut Ave Suite 5N01 Norwalk CT 06854 USA Toll Free 1 800 826 6342 USA Canada only Customer Service 1 800 622 2378 U...

Страница 3: ...nction Select Mode 9 5 6 Reset Defaults 9 5 7 Function Select Mode 10 5 8 Function 1 Enter Password 11 5 9 Function 2 Set Active Zones 11 5 10 Function 3 and 4 Set Low and High Alarms 12 5 11 Function...

Страница 4: ...Calibration 26 7 6 Enumerated Values 26 7 7 Sensor Type 26 7 8 RTD Type 26 7 9 Thermocouple Type 27 7 10 Sensor Status 27 7 11 System State 27 7 12 Process Unit 28 7 13 Alarm Type 28 7 14 Alarm Statu...

Страница 5: ...18 Table Page Table 1 Rear Panel Connections 4 Table 2 9 Pin Input Power Relay Wiring Summary 5 Table 3 Connecting Communications 7 Table 4 Function Codes 10 Table 5 Device Configuration 14 Table 6 A...

Страница 6: ...The universal input supports 9 thermocouple types J K T E R S B C and N 2 or 3 wire RTDs Pt 100 Ni 120 Cu 10 DC voltage 0 1 Vdc or DC current 0 24 mA Independent alarms are available for each zone Ea...

Страница 7: ...ian with corresponding qualifications Failure to follow all instructions and warnings may result in injury Use Copper conductors only minimum 20 AWG UL Rated for power and outputs Insulation must be r...

Страница 8: ...he case into the cutout from the front side of the panel Reinstall the two slides and two screws The length of the slides must be reduced if the monitor is to be mounted in an extra thick panel Ensure...

Страница 9: ...12A Rear Panel Connections Item Description 1 Reset Pinhole 2 Serial Connector 3 Input 7 through 12 4 Input 1 through 6 5 Supplementary Ground Point 6 Power and Alarm Connector 7 Mounting Slide Table...

Страница 10: ...AC Power or pins 5 and 9 DC Power of the 9pin power output connector as shown in Figure 3 NC L ALM1 NO C N NC ALM2 NO C 1 9 N L SW Fuse SW Or DC POWER OPTION 90 240Vac 9 36Vdc AC POWER Fuse Figure 3...

Страница 11: ...cted to the Relay common contact NC L ALM1 NO C N NC ALM2 NO C 1 9 Fuse Fuse Load Load WARNING For the low voltage power option maintain the same degree of protection as the standard high voltage inpu...

Страница 12: ...en connecting sensors follow the polarity indicated on the rear panel For Thermocouples the Negative wire is Red NA or White IEC 584 3 For Process Inputs the Negative terminal is ground For the RTD 3...

Страница 13: ...1 RUN Mode When power is applied to the unit it will automatically enter the RUN mode sequentially scanning each active zone and activating alarms if required The Main display shows the measured valu...

Страница 14: ...laying HighValues Return to Run Mode Section 5 5 Function Select Mode Enter Function Select Mode from Run Mode Section 5 6 Reset Defaults Hold all 3 buttons down for 5 seconds to reset unit to Factory...

Страница 15: ...bus Address 6 Set Scan Time 7 Set Model Options 8 Password Enable and Disable 9 Calibration A Set Alarm 1 Options B Set Alarm 2 Options C Set Low Scale D Set High Scale F Set Serial Options Table 4 Fu...

Страница 16: ...ect all of the functions will be available If the password was entered incorrectly it must be re entered by selecting Function 1 again Section 5 9 Function 2 Set Active Zones The main display is blank...

Страница 17: ...ne are independent The zone for the current alarm being edited is shown in the zone display The current alarm value for the selected zone is shown in the main display The left most digit blinks indica...

Страница 18: ...ashing digit of the Main display Selects the next digit of the Main display causing it to flash Stores the Device address and returns to the Function Select mode Series Navigation 5 Section 5 12 Funct...

Страница 19: ...ific functions C F mA mV Function Zone Series Navigation 5 Digit 1 Digit 2 Digit 3 Digit 4 Alarm Type Unit Alarm Latch Input Type TC Type RTD Type Decimal Points 0 High 0 C Latching 0 TC 0 B Pt100 0 1...

Страница 20: ...ate as soon as the input no longer meets the alarm conditions The Alarm Latch Type is overwritten by the User settings if user is selected for the Alarm Type Digit 3 selects between the available inpu...

Страница 21: ...cumstances For 2 wire RTDs Function 9 may be used to calibrate out lead wire resistance This calibration is done independently for each channel To perform lead wire calibration short the RTD that need...

Страница 22: ...d for all zones The Current Zone being edited is shown in the Zone Display The current mode for that zone is displayed in the Main Display C F mA mV Function Zone Increment the flashing digit of theVA...

Страница 23: ...plied independently for each zone The current zone being modified is displayed in the Zone Display Enter the value to be displayed at 4mA or 0V in Function C and the value to be displayed at 20mA or 1...

Страница 24: ...play causing it to flash Stores the currentVALUE display as the Serial configuration and returns to the Function Select mode This button will have no ef fect if the currentVALUE is does not match a va...

Страница 25: ...ually accessed using a one byte SLAVE address The MASTER device initiates a transaction by sending a request packet to a specific slave The SLAVE device processes the transaction and returns either re...

Страница 26: ...ister Reads When reading a dual register entity the lower order register should be used as the requested holding register with a request for a minimum of 2 registers Internally the entire entity is re...

Страница 27: ...two most significant bytes will result in an error response Data Types Number of Registers Byte Description 0 1 2 3 Boolean 1 LSB N A Zero OFF non zero ON Byte Char 1 LSB N A Entity contained in LSB o...

Страница 28: ...Version 0x0004 40004 HW Version R R Hardware version 0x0005 40005 Max Zones R R Max zones supported by device 0x0006 40006 Temperature Scale R RW Select Fahrenheit or Celsius degree 0x0007 40007 Sens...

Страница 29: ...Index Mnemonic Type Access Description 0x0180 40384 Sensor Status Zone 1 R R Zone 1 Sensor status 0x0181 40385 Sensor Status Zone 2 R R Zone 2 Sensor status 0x0182 40386 Sensor Status Zone 3 R R Zone...

Страница 30: ...Setpoint Low for alarm Base 0x04 Alarm 1 Mode R RW Enumerated alarm mode Base 0x05 Alarm 1 Latch R RW Enumerated setting toggle Base 0x06 Alarm 1 Status R RW Enumerated alarm status Base 0x07 Alarm 2...

Страница 31: ...Ohm for Zone 8 0x1d8c 47564 Zone 9 RTD offset F RW Offset Ohm for Zone 9 0x1d8e 47566 Zone 10 RTD offset F RW Offset Ohm for Zone 10 0x1d90 47568 Zone 11 RTD offset F RW Offset Ohm for Zone 11 0x1d92...

Страница 32: ...e 6 TYPE_S Thermocouple S type 7 TYPE_T Thermocouple T type 8 TYPE_N Thermocouple N type Section 7 10 Sensor Status Sensor Status 0 VALID Sensor is normal 1 OUT_OF_RANGE_LOW Sensor Reading is below va...

Страница 33: ...Alarm activated when Alarm Low SP PV Alarm High SP 3 ALARM_OFF Alarm is disabled 4 ALARM_SPLIT_A_B Alarm 1 activates Alarm relay A alarm 2 activates Alarm relay B Section 7 14 Alarm Status Alarm Stat...

Страница 34: ...Time Delay UL 248 14 listed 25 mA 250 V 300 mA 250 V Low Voltage Option Time Lag IEC 127 3 recognized 25 mA 250 V 300 mA 250 V Low Voltage Option Line Voltage Power 120 240 Vac 50 60Hz 3W Max Low Volt...

Страница 35: ...0 to 1372 C 1 0 C 1 0 C 2 0 C Type T C Copper Constantan 150 to 0 C 1 0 C 2 0 C 7 0 C 0 to 400 C 1 0 C 1 0 C 2 0 C Type T C CHROMEGA Constantan 150 to 0 C 1 0 C 2 0 C 5 0 C 0 to 1000 C 1 0 C 1 0 C 2...