Section 5.13 - Function 7 - Set Device Configuration
Function 7 sets the device configuration including the Alarm Type, Units and input
type. The default setting for Function 7 is 2204 which represents Thermocouple
Type K inputs with High/Low Latching alarms in Degrees Celsius.
Each digit in the Main Display represents a different function. Refer to the table
below for the specific functions.
ºC
ºF
mA
mV
Function
Zone
Series Navigation
5
Digit 1
Digit 2
Digit 3
Digit 4
Alarm
Type
Unit
Alarm
Latch
Input Type
TC
Type
RTD
Type
Decimal
Points
0
High
0
C
Latching 0
TC
0
B
Pt100 0
1
Low
1
F
Latching 1
RTD2
1
C
Ni120 1
2
High/
Low
2
C
Non-
Latching
2
RTD3
2
E
Cu10
2
3
Off
3
F
Non-
Latching
3
mA
3
J
3
4
User
4
mV
4
K
5
R
6
S
7
T
8
N
Table 5 - Device Configuration
14
Please note: Digit 4 is dependent upon the “Input Type” selected under Digit 3. Ex: If “TC” is selected under “Input Type” under Digit 3, Digit
4 becomes one of the following “B, C, E, J, etc.” under “TC Type.”