USING THE RPS-1in the OM-420

Omega Engineering Inc.

  

2

Stamford, CT

An integral State-of-Charge (SOC) indicator is provided which will display an approximate Battery State-of-
Charge based on battery voltage under a fixed load.  Test is actuated by depressing a momentary SOC
Test Switch.

HARDWARE / USER CONTROLS:

Figure 1 illustrates the functional blocks contained within the RPS-1. An explanation of each block follows:

MAIN POWER SWITCH

Provides ON/OFF control of the RPS-1.  In the OFF position, the batteries are disconnected from the RPS-
1 circuits (power supplies, State-of-Charge indicator, charging circuits, etc.).  This switch in either 12 VDC
or 24 VDC ON position selects how the two 12 volt gel-cell batteries are connected (parallel for 12 VDC
nominal output or series for 24 VDC nominal output). Note: For charging, the Main Power switch must be in
either the 12VDC or 24VDC position.

CHARGER INPUT

Two terminal connections are provided for connection of an external current source for charging the RPS-1
batteries.

POWER SUPPLY OUTPUTS

Two independent User programmable voltage power supply outputs (A and B) feed the twelve position
terminal strip on the right side of the unit.  The top four terminals are all connected to the A supply output
and the middle four to the B supply output.  The bottom four terminals are all connected together and to
the COMMON (circuit ground) of the two supplies.

OUTPUT VOLTAGE / MODE SWITCHES

Each of the two power supplies has an eight position DIP switch associated with it.  The top seven switches
determine the output voltage for that supply and the last switch (#8) defines the mode of operation (AUTO
or ON) for the power supply.

12 V Gel-Cell
BATTERY

12 V Gel-Cell
BATTERY

Main Power
  Switch

Battery State of
Charge light bar

Battery Charging
    circuitry

Power Supply
         A

Power Supply
         B

hl200-01.ecw

External Power
Supply Control
      Signal

+

+

-

-

Figure 2: RPS-1 Functional Block Diagram

Содержание OM-420

Страница 1: ...ange of 10 to 60C A slide switch allows the User to configure the RPS 1 for 12 or 24VDC operation Two User programmable Power Supply outputs are available which can source 7 different regulated voltag...

Страница 2: ...r the 12VDC or 24VDC position CHARGER INPUT Two terminal connections are provided for connection of an external current source for charging the RPS 1 batteries POWER SUPPLY OUTPUTS Two independent Use...

Страница 3: ...ng circuits For these two reasons ventilation around the package will maximize performance as well as minimize risk of potentially hazardous explosions WIRING The OM 420 is factory configured to use O...

Страница 4: ...tion If the voltage is less than the OUTPUT VOLTAGE SWITCH programmed setting the power supply is in current limit mode and the current load must be reduced In many applications this can be simply don...

Страница 5: ...e and mounting kit information NOTE The MAIN POWER SWITCH must be in the 24VDC or 12VDC position to allow charging BOOST CHARGE The BOOST CHARGE momentary push button switch on the RPS 1 provides init...

Страница 6: ...ternal current limiting The RPS 1 can be configured for this by placing the red pin jumper on the PCB in the EXTERNAL position See Figure 4 This RED colored jumper is located on the back of the RPS 1...

Страница 7: ...CHECK THESE CONNECTIONS BEFORE TURNING THE MAIN POWER SWITCH ON INCORRECT CONNECTION WILL RESULT IN PERMANENT DAMAGE TO THE RPS 1 TROUBLESHOOTING SYMPTOM OUTPUT VOLTAGE IS LOW PROBLEM Batteries are d...

Страница 8: ...OFF during charging SOLUTION Switch must be ON PROBLEM Batteries have insufficient charge to power charging start up circuitry SOLUTION Press and hold the BOOST CHARGE button for approximately 10 sec...

Отзывы: