OMEGA AIR RDHP 20 Скачать руководство пользователя страница 9

3.2 Specifications 

 
TECHNICAL SPECIFICATIONS 

Max. operating pressure 

45 bar

g

 

Max. inlet air temperature 

55 °C (for temperature ≠ 

35 

°C apply correction factor)

 

Operating ambient temperature 

°C to 45

 

°C (for temperature >

 25 

°C apply correction factor)

 

Storage conditions 

1 °C to 65 °C, <90 % relative humidity

 

Pressure dew point 

+ 3 

°C

 

Filter requirement (inlet) 

Prefilter 3 

μ

Communication 

MODBUS 

Digital input 

Remote ON/OFF 

Digital output

 

Alarm 

Condenser type 

Air cooled 

Compressor operation 

Non-cycling 

Condensate drain 

Timer controlled (Automatic optional) 

Refrigerant

 

R134a 

 

Protection class (controller front) 

IP 65 

 

 
MATERIALS 

Casing 

Carbon steel  

Casing corrosion protection 

Epoxy powder paint 

Evaporator 

Brazed plate stainless steel 

Evaporator insulation 

Flexible elastomeric foam 

Condenser 

Aluminium fin and copper tube 

Compressor 

Carbon steel 

Refrigerant piping 

Copper 

Controller enclosure 

Plastic 

 
SIZES 

 

Compressed air 

Electrical connection 

Ambient air 

Refrigerant 

Dimensions & Mass 

Model 

(3)

Flow 

Connection 

Pressure 

drop 

Power supply 

(4)

Power/ 

Consumption 

Cooling 

flow 

Heat 

rejec. 

Type 

Mass 

 W x L x H 

Net 

 

m

3

/h 

 

bar 

Ph~V-Hz 

kW 

m

3

/h 

kW 

 

kg 

mm 

kg 

RDHP 20 

20 

G 3/8” BSP

-F 

<0,3 

1~230-50* 

0,170 / 0,135 

350 

0,12 

R134a 

0,20 

352 x 485 x 499 

24 

RDHP 35 

35 

G 3/8” BSP

-F 

<0,3 

1~230-50* 

0,170 / 0,135 

350 

0,21 

R134a 

0,23 

352 x 485 x 499 

24 

RDHP 50 

50 

G 3/8” BSP

-F 

<0,3 

1~230-50* 

0,170 / 0,135 

350 

0,30 

R134a 

0,34 

352 x 485 x 499 

25 

RDHP 75 

75 

G 3/8” BSP

-F 

<0,3 

1~230-50/230-60 

0,40 / 0,25 

350 

0,47 

R134a 

0,38 

352 x 485 x 499 

26 

RDHP 100 

100 

G 3/8” BSP

-F 

<0,3 

1~230-50/230-60 

0,40 / 0,25 

350 

0,62 

R134a 

0,58 

352 x 485 x 499 

31 

RDHP 140 

140 

G 1/2” BSP

-F 

<0,3 

1~230-50/230-60 

0,50 / 0,38 

700 

0,83 

R134a 

0,61 

356 x 552 x 684 

44 

RDHP 180 

180 

G 1/2” BSP

-F 

<0,3 

1~230-50/230-60 

0,60 / 0,45 

700 

1,05 

R134a 

0,65 

356 x 552 x 684 

49 

RDHP 235 

235 

G 1/2” 

BSP-F 

<0,3 

1~230-50/230-60 

0,60 / 0,45 

700 

1,37 

R134a 

0,73 

356 x 552 x 684 

53 

RDHP 300 

300 

G 3/4” BSP

-F 

<0,3 

230V, 50 Hz* 

0,73 / 0,60 

700 

1,32 

R134a 

0,90 

356 x 552 x 684 

62 

RDHP 380 

380 

G 3/4” BSP

-F 

<0,3 

230V, 50 Hz* 

0,73 / 0,60 

700 

1,67 

R134a 

0,95 

356 x 552 x 684 

65 

RDHP 480 

480 

G 1” BSP

-F 

<0,3 

1~230-50/230-60 

1,15 / 0,90 

1100 

2,10 

R134a 

1,10 

495 x 589 x 827 

88 

RDHP 600 

600 

G 1” BSP

-F 

<0,3 

1~230-50/230-60 

1,15 / 0,90 

1100 

2,64 

R134a 

1,20 

495 x 589 x 827 

91 

RDHP 750 

750 

G 1” BSP

-F 

<0,3 

1~230-50/230-60 

1,20 / 1,00 

1100 

3,23 

R134a 

1,40 

495 x 589 x 827 

105 

RDHP 950 

950 

G 1” BSP

-F 

<0,3 

1~230-50/230-60 

1,30 / 1,10 

2200 

4,09 

R134a 

1,60 

491 x 708 x 973 

111 

 Larger sizes available upon request 

 

(3)

 

Nominal condition: inlet flow 20 

°

C at 1 bar

a

, ambient 25 °C,

 dryer inlet 35

°

C at 40 bar

g

3 °C 

pressure dew point (-36,6 

°C atmospheric).

 

(4)

 For 60 Hz 20 % more than stated. Consumption at nominal conditions. 

*Special 60 Hz version available. 

 

 

 

 

Содержание RDHP 20

Страница 1: ...before installation or use The proper and safe operation of the refrigeration air dryer is ensured only by following the recommendations and conditions stated in the instructions For additional questi...

Страница 2: ...maintenance is limited to a few checks and cleanings as shown in the continuation of this manual These instructions must always be present at the unit and be available for the entire operating life o...

Страница 3: ...15 5 4 3 RDC 2 MODBUS COMMUNICATION 17 5 5 EXPANSION VALVES 18 5 6 TIMED CONDENSATE DRAIN 18 5 7 SAFETY FUNCTIONS 19 5 7 1 LOW PRESSURE SWITCH 19 5 7 1 SAFETY FUNCTIONS OF RDC 2 19 5 8 FILTER DEHYDRA...

Страница 4: ...rmation Please fill in the fields carefully Correct data enables proper and efficient maintenance of the device selection of suitable spare parts and technical support 1 2 Information on the supplier...

Страница 5: ...yers 1 4 Refrigeration air dryers Refrigeration air dryers are the best choice in all standard applications where pressure dew point 3 C suffices Examples of such applications are process air in the p...

Страница 6: ...t the dryer is vented and not under pressure this also includes the closest components of the installation in front and behind the dryer and that the dryer is not connected to an electrical source Do...

Страница 7: ...eck and follow the local regulations for lifting and transporting heavy objects In the event of fire do not use extinguishing water on the dryer and nearby objects Wear suitable protective equipment e...

Страница 8: ...1 Components 1 Heat exchanger 3in1 7 Switch 2 Condenser 8 Capillary tube 3 Compressor 9 Sensor for fan operation 4 Timed condensate drain 10 Filter dehydrator 5 Controller 6 Hot gas bypass valve Figur...

Страница 9: ...1 230 50 0 170 0 135 350 0 21 R134a 0 23 352 x 485 x 499 24 RDHP 50 50 G 3 8 BSP F 0 3 1 230 50 0 170 0 135 350 0 30 R134a 0 34 352 x 485 x 499 25 RDHP 75 75 G 3 8 BSP F 0 3 1 230 50 230 60 0 40 0 25...

Страница 10: ...INAL FLOW CAPACITY x COP x CAT x CIN x CDP OPERATING PRESSURE DEW POINT bar 15 20 25 30 35 40 45 C 3 5 7 10 psi 218 290 363 435 508 580 652 F 37 4 41 44 6 50 COP 0 57 0 7 0 8 0 88 0 94 1 1 05 CDP 1 1...

Страница 11: ...wer temperature than the input air Refrigeration circuit The refrigerant enters the compressor and then enters the condenser at high pressure where it transfers heat to the ambient air and condenses T...

Страница 12: ...e compressor cools condenses and changes the aggregate state from the gaseous to the liquid The condenser is a pipe in which the refrigerant is flowing and on which fins are placed The heat transfer i...

Страница 13: ...ear on the display The alarm automatically turns off when the dryer is restarted and is operating properly a Sensors used for regulation 1 Tdew Dew point temperature 2 Tcomp Compressor temperature 3 T...

Страница 14: ...FF ON via In Remote by changing the parameter 13 Remote control from 0 to 1 When the circuit is connected the controller goes to OFF state when the circuit is disconnected the controller is in ON stat...

Страница 15: ...lue 5 5 Min Compressor OFF time yes Increase value Decrease value 1 min 6 no Increase value Decrease value 2 7 no Increase value Decrease value 5 8 no Increase value Decrease value 0 9 no Increase val...

Страница 16: ...er number 5 You will see the default parameter value 1 min Change it to a desired value if necessary if not skip the next step Wait a couple of seconds the controller exits automatically Turn off the...

Страница 17: ...022 T_Dew R_ONLY T_Dew X 200 10 C 40023 T_Comp R_ONLY T_Comp X 200 10 C 40024 T_Cond R_ONLY T_Cond X 200 10 C 40025 P_Cond R_ONLY P_Cond X 10 Bar 40026 Digital Input status R_ONLY 0 contact open 1 con...

Страница 18: ...justed without the load on the dryer Rotate the screw until the following value is reached Hot gas setting R134 a pressure 2 0 barg 0 1 bar 5 6 Timed condensate drain Condensate drain consists of two...

Страница 19: ...eck the hot gas bypass valve Lt Low dew point temperature Check that the temperature sensor is correctly inserted into its position check the cooling system sealing charging check the hot gas bypass v...

Страница 20: ...o the interior components of the dryer the installation and use may result in injury or death Check the dryer for any visible damage after removing the packaging If the refrigeration air dryer is dama...

Страница 21: ...vibration refers to the floor and pipes For maintenance and servicing provide sufficient space for uninhibited work around the unit 1 m The ventilation grilles of the device must not be covered for th...

Страница 22: ...ressure vessel 3 Condensate Separator 8 Filter 4 Pre filter min 5 micron 9 Condensate drain 5 Bypass air valve Type A installation is recommended when the compressor operates at a reduced interruption...

Страница 23: ...osition of the holes in the illustration is shown maximum size M8 The pipe connections for the compressed air in the front and back of the dryer must be fitted with suitable valves that allow the inde...

Страница 24: ...bypass air circuit is closed and that the dryer is insulated from the system Check and ensure that the condenser is clean free of impurities 10 2 Start up Connect the dryer to the power supply Connect...

Страница 25: ...nance work on the refrigeration air dryer turn it off and wait for at least 30 minutes for it to cool down Some components can reach high temperature during operation Avoid contact with these componen...

Страница 26: ...s The condensate was not drained from the dryer Check the electrical installation Dew point is too low the condensate is frozen and blocks the air flow The compressed air pressure is too low and the c...

Страница 27: ...1 1 1 1 1 Fan blade 2101865 1 1 1 1 1 Fan diffuser 2101863 1 1 1 1 1 Hot gas by pass valve 2204737 1 1 1 1 1 1 1 1 2204746 1 1 2204736 1 1 2204748 1 1 Filter 2101578 1 1 1 1 2100441 1 1 2100597 1 1 21...

Страница 28: ...r property resulting from improper use or inadequate maintenance of the device and is limited solely to production errors When claiming a warranty you must provide information from the identification...

Страница 29: ...29 16 Maintenance notebooks MAINTENANCE TYPE DATE SIGNATURE NOTES First installation...

Страница 30: ...30...

Страница 31: ...31 17 Drawings of RDHP refrigeration air dryers RDHP 20 100...

Страница 32: ...32 RDHP 140 235...

Страница 33: ...33 RDHP 300 480...

Страница 34: ...34 RDHP 600 950...

Страница 35: ...35 18 Electro schemes of RDHP refrigeration air dryer RDHP 20 180...

Страница 36: ...36 RDHP 235 950...

Страница 37: ...Compressed air refrigeration dryer Is in conformity with the following directives Pressure Equipment Directive PED 2014 68 EU Electromagnetic Compatibility Directive EMC 2004 108 EC EN 61000 6 3 2007...

Отзывы: