5.4 Controller RDC 2
At startup, the controller shows the time remaining until compressors starts by displaying COMP TIME
X MIN. The value X can be changed by changing the parameter no. 5.
The controller RDC 2 shows the temperature of the dew point reached by the refrigeration air dryer in
the normal operation. By pressing the UP (
▲
) button, the outlet temperature of the compressor is
displayed. By pressing the DOWN (
▼
) button, the condensation temperature is displayed (the
temperature sensor is connected) or the condensation pressure is displayed (the pressure sensor is
connected). In case of fault, an alarm will appear on the display. The alarm automatically turns off
when the dryer is restarted and is operating properly.
a)
Sensors used for regulation:
1)
T
dew
= Dew point temperature
2)
T
comp
= Compressor temperature
3)
T
cond
ali p
cond
= Condensation temperature or pressure (4-20 mA)
b)
Regulated components:
1)
Fan (ON/OFF)
2)
Compressor (ON/OFF)
3)
Drain (ON/OFF)
c)
Operation of fan and compressor
1)
Normal operation:
•
The compressor is always running
•
The fan is regulated based on measured condensation temperature or pressure
•
Dew point temperature is displayed.
2)
Alarm operation
•
In alarm state the normal operation is overridden.
•
If more alarms are activated the last one activated has priority with display and
fan/compressor operation. All other active alarms have to be resolved before
continuing in normal operation.
•
Alarm is displayed.
Содержание RDHP 20
Страница 29: ...29 16 Maintenance notebooks MAINTENANCE TYPE DATE SIGNATURE NOTES First installation...
Страница 30: ...30...
Страница 31: ...31 17 Drawings of RDHP refrigeration air dryers RDHP 20 100...
Страница 32: ...32 RDHP 140 235...
Страница 33: ...33 RDHP 300 480...
Страница 34: ...34 RDHP 600 950...
Страница 35: ...35 18 Electro schemes of RDHP refrigeration air dryer RDHP 20 180...
Страница 36: ...36 RDHP 235 950...