CORRECTION FACTORS
To calculate the correct capacity of a given dryer based on actual operating conditions, multiply the nominal
inlet flow by the appropriate correction factor(s). CORRECTED CAPACITY = NOMINAL FLOW CAPACITY x C
OP
x
C
AT
x C
IN
x C
DP.
OPERATING PRESSURE
DEW POINT
[bar]
15
20
25
30
35
40
45
°C
3
5
7
10
[psi]
218
290
363
435
508
580
652
°F
37,4
41
44,6
50
C
OP
0,57
0,7
0,8
0,88
0,94
1
1,05
C
DP
1
1,09
1,19
1,37
INLET TEMPERATURE
AMBIENT TEMPERATURE
°C
≤25
30
35
40
45
50
55
°C
≤25
30
35
40
45
°F
77
86
95
104
113
122
131
°F
77
86
95
104
113
C
IN
1,2
1,12 1,00 0,83 0,69 0,59 0,50
C
AT
1
0,96 0,9 0,82 0,72