Troubleshooting
Compressor runs, but
the temperature in the
showcase is high.
Circulating temperature is
too high.
Adjust the thermostat
properly.
Ask for authorized service
department to check and
repair it.
Too much dust and dirt on
the condenser.
Clean it on time.
Frost on the evaporator is
too thick.
Stop the machine
to defrost. Set the
temperature higher.
Thermostat is out of work. Replace.
Condenser fan does not
run.
The capacitor of the fan is
out of work.
Replace.
The ball-bearing of the
fan motor lacks oil.
Fill oil.
The winding of the fan
motor is damaged.
Replace.
Compressor starts/stops
frequently.
The winding of the
compressor is short
circuit.
Check with a multi meter,
replace the compressor.
Poor contact of the
socket.
Repair or replace.
The fan of the evaporator
does not work.
The fan motor is
damaged.
Replace.
Warning: If the machine has any problems or has been damaged, do not try to repair or replace it by
yourself. Please contact Omcan technical service at 1-800-465-0234.