background image

923427002_09_002

Page 4 from 4

4

5

6

INSTALLATION INSTRUCTIONS

2

A

Base plastic

Cable entry channels

Luminaire mounting holes

3

B

1

A

B

Diffusor

Reflector

Base plastic

N

L

L

1

1   To install the luminaire you must dismantle it into 3 parts.
2   Place a flat blade screwdriver in the area 

Α 

to release the diffusor’s 

     plastic hook.
3

   

Place a flat blade screwdriver in the area 

to release the reflector’s 

     plastic hook.
4   Use the included mounting parts to mount the base plastic. Pass 
     the mains cable through a cable entry channel. The luminaire 
     must be connected to a permanent electrical installation to ensure 
     the immobilization of the cable.
5   Place the battery’s connector to the corresponding connector on the
     P.C.B.
6   Connect the mains cables to the respective detachable terminal 
     block. 

Ν for neutral, L for live wire and L1 for the maintained 

     operation

. The L1 wire can be connected to an external switch to 

     control the maintained or non maintained operation of the luminaire. 
     For permanent maintained operation use two wires to power the 
     luminaire, Ν for neutral and L for live wire, and link the L and L1.
7   Refit the removed parts in steps 2 and 3 (mind the correct orientation) and the luminaire is ready to operate.

N

N

L

L

External 

switch

Link

Controled operation of the luminaire

Permanent maintained operation 

N

N

L

L

L1

L1

NOTE!! 
After finishing the installation you must power the luminaire at least for 24 hours for battery 
charging to perform the nominal autonomy. 

Battery replacement. 
It can be done only by a competent person and after the mains interruption.

1. Follow the step 2 and 3 of the installation procedure.
2. Disconnect the connector and remove the old battery.
3. Connect the new battery with the same type (step 5 of the installation procedure) and place it in
    the position of the old one.

NOTE: 

LED= Light Emitting Diode

LABELING EXPLANATION:
X: 

Self contained                  

1: 

Maintained (*)

A: 

Including test device        

480: 

480min duration

(*) Maintained operation: The luminaire lights its illumination source, when it is powered by the 
mains power supply or not.