Figure
2.
Connection diagram of a detector
NC
C
NO
N
+
L
OUT
GND
Z+
Z -
+VS
GND
S
EXTERNAL
BUZZER
Sensor
JMP1
JMP2
JMP3
L N
~230 V
A
B
1
1
1
SENSOR
BS-655
BS-542
5K6
+VS
GND
S
BS-692
GND
+12V
K
Θ
BS-660
0,5W
Figure 3a and 3b shows the connection of
multiple detectors in a network connection , for
covering a larger area and using one
12
VDC NO
electro-valve or one
12
VDC NC electro-valve
Attention!!
The position link of JMP1 set the
relay status.
If a link is set on A ( figure 3B ) the relay is
energized (NO) in normal condition and on alarm
or fault condition the relay is not energized.
The oppisite occurs if a link is set on B ( figure
3A).
ATTENTION:
If you use electrovalves 230VAC
you can use a fire-siren 230VAC BS-546 and
BS-542 . The connection of BS-546 show in
figure 5. If you use electrovalves 12VDC you can
only use BS-542 .
ATTENTION!!
The devices must not be tested
using gas filled lighters because the sensor will
be destroyed.
NC
C
NO
N
+
L
OUT
GND
Z+
Z -
JMP1
A B
1
NC
C
NO
N
+
L
JMP1
A B
1
NC
C
NO
N
+
L
JMP1
A B
1
...
E.V. 12VDC N.C.
1st
Vth
2
nd
Figure
3.
Connecting multiple detectors in a network and using one
electro-valve
12
VDC N.C.
921691000_
09
_0
16
Page
3 from
5