Technical Specifications

BS-

1

634

4 zone fire

detection panel

BS-

1

636

6 zone fire

detection panel

Mains power supply

220-240V AC / 50-60Hz

Two

 12V Lead acid sealed  

2.6

Ah

Stabilized power supply  

27

.

6

V / max. 400mA

Two  24V circuits that are monitored for open and short circuit conditions 

(maximum current 300mA each). Each output is protected  

with a self-reseting electronic fuse.

 2

4

VDC ( ±3VDC)  permanent output  with maximum current output  0.3 A

The output is protected with a self-reseting electronic fuse.

ABS - polycarbonate

Consumption

Battery type

Charging circuit

Zone circuits

Alarm circuits

Output   24P

Construction material

2 circuits monitored for

short and open circuit

conditions (maximum current 35mA)

 

24

VDC ( ±3VDC)  reset interrupted output  with maximum current output  0.3 A

The output is protected with a self-reseting electronic fuse.

Output  24M

 

Three

 relay

s

 contacts are rated at  30VDC  and 

5

A maximum 

each. Under no circumstances should voltages or currents outside limits

 be connected.  All relays output must be protected  with a fuse of the same rating.

Outputs Relays

325 x 240 x 85 mm

ΕΝ 54-2, ΕΝ 54-4

2 years

Dimensions

Weight

Produced in accordance to

Guarantee

Up to  95% relative humidity

Humidity

o

0 to 50  C

Operation temperature

The total output current ( zones circuits, siren circuit, outputs 24P, 24M) 

must not exceed 600mA.

(ImaxA = ImaxB = 600mA, Imin = 30mA)

Total load

IP30

1Ohm

900mA

21V

Cables for fire rated cables systems such a FIP200,MICC, PYROFIL

The panel has only one serviceable fuse to protect incoming mains supply. 

This fuse is 

630

  must be replaced with a fuse 

T

mAL250V

of the same type and rating

IP

Battery maximum internal
resistance Rimax

Battery cut of voltage

Maximum current
batteries discharge

Cables

Fuse ratings

4 circuits monitored for

short and open circuit

conditions (maximum current 35mA)

6 circuits monitored for

short and open circuit

conditions (maximum current 35mA)

50VA

Autonomy

72 hours (Maximum connected detectors 72 and 

no load at output 24VM and 24VP)

BS-

1

63

2

zone fire

detection panel

921163600_09_022

1360gr (3080gr 

with battery

1350gr (3070gr 

with battery

1345gr (3065gr 

with battery

Содержание BS-1632

Страница 1: ...12V 2 6Ah All functions and indications are according to European Norms EN 54 2 and EN 54 4 Top cover retaining screws Control Keyboard and indication leds Mounting holes Battery compartment two 920 M...

Страница 2: ...respond to the siren outputs If a siren out has a short circuit or open circuit then the corresponding LED will blink If a siren is disabled the corresponding LED will light The next group of indicato...

Страница 3: ...iren 1 and Siren2 LED lights for the siren 2 Using the keys 1 and 2 we can enable or disable the respective sirens The disabled sirens have a LED lighted The panel exits this mode if no key is pressed...

Страница 4: ...nd corresponding functions 921163600_09_022 Fault zone 1 Alarm zone 2 Alarm zone 1 Without Delay 30 second Delay 60 second Delay 90 Second Delay LED ON LED OFF LED OFF LED OFF LED OFF LED OFF LED ON L...

Страница 5: ...res with a cross section cable of 1 5mm Page 5 from 10 Figure 2 Connecting 4 detector bases to zone 1 Each base can accept BS 655 BS 660 or BS 657 detectors A remote indication LED BS 572 is connected...

Страница 6: ...larm condition ATTENTION The relays are rated at 30VDC and 5A maximum No 230VAC signals can be connected to these relays Siren Sounder Connections Each panel offers 2 independent circuits for connecti...

Страница 7: ...sed is 2 5mm Connecting the mains power supply 220 240V AC The panel has holes on the back side for all the wiring to pass through You can connect cables with max conductor diametre of 2 5mm to the pa...

Страница 8: ...r is deactivated and the LED is turned off When a siren output has an open circuit then the internal buzzer is activated and the corresponding fault LED lights If the problem is corrected then the buz...

Страница 9: ...rrents outside limits be connected All relays output must be protected with a fuse of the same rating Outputs Relays 325 x 240 x 85 mm 54 2 54 4 2 years Dimensions Weight Produced in accordance to Gua...

Страница 10: ...erini P C 60300 P O Box 06 Eginio Pierias Greece www olympia electronics gr info olympia electronics gr CONVENTIONAL 6 ZONE FIRE ALARM PANEL INSTALL IN ACCORDANCE WITH PRODUCT MANUAL 921163600_08_021...

Отзывы: