Installation

The installation of the panel must be carried out by qualified personnel only.
Disconnect power before servicing.
Never insert or remove boards or componets with the power on.
During installation use grounded antistatic wrist band to protect this equi

p

ment form ESD.

The panel must be installed permanetly. It is not allowed to connect the device directly to any socket-
outlet.

Mounting the panel to the wall

The site chosen for the location of the panel should be clean and dry and not subject to shock or 
vibration.
In page 1 shows the mounting holes of the panel. 
The panel must be placed above 1m from the floor and and 1m below the ceiling and must have 
distance 30cm from any other devices. No other power lines must pass behind the panel, only the 
supply cables of the panel.

Cabling

In order to meet EMC requirements , connections of peripherals to the panel must be done using 
shielded cables.

Each screen or shield braid must properly be  connected  to the earth terminal block provided, thus 
ensuring the shortest posible path. The maximum conductor diameter size, which can be 

us

ed, is 

2,5mm²

Connecting the mains power supply

(220-240V AC)

The panel has holes on the back side for all the wiring to pass through. You can connect cables with 
max. conductor diametre of 2.5mm to the panels terminal blocks.
The mains power supply wiring must use a double insulation cable.

The main supply must include an earth conductor connected to the fixed installation 
earthing system of the building.

 The connection with the mains power supply must be 

done to the terminal blocks located on the panels up left area Figure 8 .

Battery connection

The battery compartment has the appropriate dimensions for Α-9

20

 

batter

ies

 of 

Ol

ympia 

E

lectronics

.

The charging unit on PCB is also calculated for the specific batter

ies

Replace the

m

 only with batter

ies

 of the same type.

From the PCB, are connected two battery wires with a special terminal on the 
edge. They must be connected to the two battery poles. Connect the black wire 
to the negative pole (marked (-) or a black mark)

,

 the red wire to positive pole 

(marked (+) or a red mark)

 and connect the included wire for the link as showed 

in the side figure

.

Figure 7.

 

Connection diagram of BS-489 telephone operator.

-

+

24_P

 

Fire Detection

 Panel

Connecting the BS-489 telephone operator

Page 7 from 

10

NO

ALARM

 

C NC NO

FAULT

 

C NC

Panel connection

Link

921163600_09_022

Содержание BS-1632

Страница 1: ...12V 2 6Ah All functions and indications are according to European Norms EN 54 2 and EN 54 4 Top cover retaining screws Control Keyboard and indication leds Mounting holes Battery compartment two 920 M...

Страница 2: ...respond to the siren outputs If a siren out has a short circuit or open circuit then the corresponding LED will blink If a siren is disabled the corresponding LED will light The next group of indicato...

Страница 3: ...iren 1 and Siren2 LED lights for the siren 2 Using the keys 1 and 2 we can enable or disable the respective sirens The disabled sirens have a LED lighted The panel exits this mode if no key is pressed...

Страница 4: ...nd corresponding functions 921163600_09_022 Fault zone 1 Alarm zone 2 Alarm zone 1 Without Delay 30 second Delay 60 second Delay 90 Second Delay LED ON LED OFF LED OFF LED OFF LED OFF LED OFF LED ON L...

Страница 5: ...res with a cross section cable of 1 5mm Page 5 from 10 Figure 2 Connecting 4 detector bases to zone 1 Each base can accept BS 655 BS 660 or BS 657 detectors A remote indication LED BS 572 is connected...

Страница 6: ...larm condition ATTENTION The relays are rated at 30VDC and 5A maximum No 230VAC signals can be connected to these relays Siren Sounder Connections Each panel offers 2 independent circuits for connecti...

Страница 7: ...sed is 2 5mm Connecting the mains power supply 220 240V AC The panel has holes on the back side for all the wiring to pass through You can connect cables with max conductor diametre of 2 5mm to the pa...

Страница 8: ...r is deactivated and the LED is turned off When a siren output has an open circuit then the internal buzzer is activated and the corresponding fault LED lights If the problem is corrected then the buz...

Страница 9: ...rrents outside limits be connected All relays output must be protected with a fuse of the same rating Outputs Relays 325 x 240 x 85 mm 54 2 54 4 2 years Dimensions Weight Produced in accordance to Gua...

Страница 10: ...erini P C 60300 P O Box 06 Eginio Pierias Greece www olympia electronics gr info olympia electronics gr CONVENTIONAL 6 ZONE FIRE ALARM PANEL INSTALL IN ACCORDANCE WITH PRODUCT MANUAL 921163600_08_021...

Отзывы: