background image

31

APPENDIX A - CONTROL MODULE

— If flame rod or bracket is bent out of position, restore 

to correct position.

STEP 3:

 Check spark ignition circuit. 

Disconnect ignition cable at SPARK terminal on module.

WARNING

Electrical shock hazard. Ignition circuit generates 

over 10,000 volts. Turn OFF electrical power 

supply at service panel before making electrical  

connections.  Failure to do so could result in death 

or serious injury.

!

  

Energize module and listen for audible sparking noise. 

When operating normally, there should be buzzing noise 

turns on and off twice per second for duration of 1–7 

seconds, depending on model.

STEP 4:

 Verify pilot and main burner light-off.

• Initiate call for heat. Turn thermostat above room 

temperature.  Ignition sequence may be delayed by 

thermal purge until boiler water temperature is below 

140°F (60°C)

• Watch pilot burner during ignition sequence.  

— Verify ignition spark continues after pilot is lit.
— Verify pilot lights and spark stops, verify main  

burner does not light.

• 

If so, ensure adequate flame current as follows.

— Turn off boiler at circuit breaker or fuse box.

— Clean flame rod with emery cloth.

— Verify electrical connections are clean and tight. 

Replace damaged wire..

— Check for cracked ceramic insulator, which can 

cause short to ground, and replace igniter-sensor if 

necessary.

— At gas valve, disconnect main valve wire from MV 

terminal.

— Turn on power and set thermostat to call for heat. Pilot 

should light, main burner will remain off because main 

valve actuator is disconnected.

— Check pilot flame. Verify it is blue, steady and 

envelops 3/8 to 1/2 in. [10 to 13 mm] of flame rod. 

See Figure 19 for possible flame problems and causes. 

— If necessary, adjust pilot flame by turning pilot 

adjustment screw on gas control clockwise to decrease 

or counterclockwise to increase pilot flame. Following 

adjustment, always replace pilot adjustment cover 

screw and tighten firmly to assure proper gas control 

operation. Figure 16, page 20. 

— Set temperature below room set-point to end call for 

heat.

• Recheck ignition sequence as follows.

— Reconnect main valve wire.
— Adjust thermostat above room temperature.
— Verify ignition sequence at burner.
— If spark does not stop after pilot lights, replace 

module.

— If main burner does not light or if main burner lights 

and system locks out, check module, ground wire and 

gas control as described in troubleshooting table. See 

Table 7, Page 30.

Figure 19 - Troubleshooting Pilot Flame

Correct Pilot Flame: 3/8 to 1/2 inch in flame. 

See Figure 16, Page 21.

Содержание OMGC-8D

Страница 1: ...INSTALLATION OPERATION MAINTENANCE MANUAL C S A Certified For Natural Gas Or Propane Models OMGC 8D OMGC 8DP OMGC 9D OMGC 9DP An ISO 9001 2008 Certified Company Tested For 50 psi ASME Working Pressure...

Страница 2: ...IONS Table 1 Dimensions BOILER MODEL NUMBER DIMENSIONS INCH FLUE DIAMETER A WIDTH OMGC 8 7 27 OMGC 9 7 30 Add 5 to height for vent Damper Figure 1 Dimensions Minimum acceptable height for Low Water Cu...

Страница 3: ...ments such as intermittent system operation extensive piping systems etc 3 Mbh 1 000 Btuh British Thermal Unit Per Hour Ratings marked Net AHRI Ratings indicate amount of remaining heat input used to...

Страница 4: ...Read this manual and understand all requirements before beginning installation SAFETY SYMBOLS WARNINGS The following defined symbols are used throughout this manual to notify the reader of potential...

Страница 5: ...2 Where required by the authority having jurisdiction the installation must conform to the Standard for Controls and Safety Devices for Automatically fired Boilers ANSI ASME CSD 1 3 Boiler series is...

Страница 6: ...cted indoor spaces All Outdoor Air Provide permanent opening s communicating directly or by ducts with outdoors A Two Permanent Opening Method Provide opening commencing within 12 inches of top and se...

Страница 7: ...igure 2 Use or larger pipe Use pipe suitable for temperatures of 375 F 191 C or greater Individual boiler discharge piping shall be independent of other discharge piping Size and arrange discharge pip...

Страница 8: ...e LOW WATER TEMPERATURE AND LARGE WATER CONTENT SYSTEM See Figures 6 and 7 Page 10 Significant condensation may form in boiler and or venting system if boiler is operated for long period of time with...

Страница 9: ...9 Figure 5 Chilled Water Piping Figure 4 Typical Hot Water Piping 6 CONNECTING SUPPLY AND RETURN PIPING...

Страница 10: ...10 Figure 6 BYPASS PIPING CIRCULATOR ON SUPPLY Figure 7 BYPASS PIPING CIRCULATOR ON RETURN Bypass Piping Required For High Mass Large Water Content Systems 6 CONNECTING SUPPLY AND RETURN PIPING...

Страница 11: ...ugged by using plug supplied with vent damper 1 Position furnished vent damper on top of flue outlet collar Fasten damper securely to flue outlet collar with sheet metal screws Verify damper blade has...

Страница 12: ...fireplace dampers 4 Place in operation the appliance being inspected Follow the lighting instructions Adjust thermostat so appliance will operate continuously 7 CHIMNEY AND VENT PIPE CONNECTION 5 Tes...

Страница 13: ...r indicator points to open position Turn thermostat or controller down again and check damper position indicator returns to closed position Vent Damper Manual Operation Vent damper may be placed in op...

Страница 14: ...ller Two stage regulation should be used by propane installer Propane gas piping should be checked out by propane installer CHECKING GAS PIPING DANGER Fire Hazard Do not use matches candles open flame...

Страница 15: ...ermostat on outside wall 3 Do not install a thermostat where it will be affected by drafts hot or cold pipes sunlight lighting fixtures televisions a fireplace or a chimney 4 Check thermostat operatio...

Страница 16: ...ntegrated High Limit Electronic Ignition Control 240008781 I Inducer is not an option WARNING Modification substitution or elimination of factory equipped supplied or specified components may result i...

Страница 17: ...17 11 WIRING DIAGRAMS Figure 13 Integrated High Limit Electronic Ignition Control 240008781 PILOT FLAME SENSOR...

Страница 18: ...S Figure 14 Integrated High Limit Electronic Ignition Control 240008781 WARNING Modification substitution or elimination of factory equipped supplied or specified components may result in personal inj...

Страница 19: ...repeat this process Repeat until you have covered every radiation units in the system ending up at highest unit in system If your units have automatic vents manual venting is unnecessary but it will...

Страница 20: ...rol knob slightly and turn clockwise to OFF Do not force WARNING If you do not follow these instructions exactly a fire or explosion may result causing property damage personal injury or loss of life...

Страница 21: ...y turning thermostat to lowest setting for one minute then back to normal setting ADJUST PILOT BURNER Pilot flame should surround 3 8 to 1 2 of the pilot sensor See Figure 16 If flame needs adjusting...

Страница 22: ...degrees C After setting limit control to limit setting check to see if it shuts off gas supply to burners Turn your thermostat up to call for heat and let boiler run until temperature of water reache...

Страница 23: ...T PIPE Venting and piping should be checked at least once a season If vent piping shows any sign of leaking replace immediately WATER SYSTEM If system is to remain out of service during freezing weath...

Страница 24: ...inals and wire joints Rollout switch blown Have your service agent check heat exchanged for blockage Replace rollout switch with exact replacement Blocked vent blown Have your service agent check vent...

Страница 25: ...nstalled in supply line It will eliminate air from water before it reaches radiators and bleed off this air MAIN AIR VENT FOR DOWN FLOW SYSTEMS OR DIAPHRAGM TYPE EXPANSION TANK Before system is filled...

Страница 26: ...ed vent safety switch must be reset manually after switch has cooled off by pushing reset button down Check venting system and chimney for blockage when restoring system to operating condition DO NOT...

Страница 27: ...b is fully inserted in well and is not loose Refer to enclosed addendum for wiring instructions when using indirect hot water heater A 3 Adjusting Settings To discourage unauthorized changing of setti...

Страница 28: ...retry Flame signal was lost during state 7 or 8 and delay is called before retry 32 second delay 13 Soft lock out Soft lockout duration is one hour may override with manual reset 14 Hard lock out Man...

Страница 29: ...and display On retry models wait for retry or reset at thermostat Check for correct installation and wiring before replacing any component Control module cannot be repaired If it malfunctions it must...

Страница 30: ...umber of retries exceeded Soft lockout Soft lockout is reset after one hour if alarm reason disappears 63 Soft lockout maximum number of recycles exceeded Soft lockout 64 Soft Lockout electronics fail...

Страница 31: ...nnections are clean and tight Replace damaged wire Check for cracked ceramic insulator which can cause short to ground and replace igniter sensor if necessary At gas valve disconnect main valve wire f...

Страница 32: ...ECR International 2201 Dwyer Avenue Utica NY 13501 web site www ecrinternational com...

Отзывы: