Boilers connecting to gas vents or chimneys, vent 

installations shall be in accordance with “Venting of 

Equipment”, of the National Fuel Gas Code, ANSI 

Z223.1/NFPA 54 or “Venting Systems and Air Supply 

for Appliances,” of the Natural Gas and Propane 

Installation Code, CAN/CSA B149.1, or applicable 

provisions of the local building codes. 

Check Your Chimney

It must be clean, right size, properly constructed and 

in good condition.  

Chimney Sizing

Chimney sizing, and vent installation must be in 

accordance with The National Fuel Gas Code, ANSI 

Z223.1/NFPA 54 or CAN/CSA B149.1, or applicable 

provisions of local building codes.

This is a high efficiency boiler with low stack 

temperature. Following recommendations are in 

addition to requirements of the National Fuel Gas 

Code.
1. Type B double wall vent pipe is recommended for 

vent connector. Single wall vent connectors should 

not be used unless following conditions are true:
a) Except for basement, boiler is not installed in 

unheated space.

b) Total horizontal portion of vent connector, not 

including elbows is less than 5 feet in length.

2. Outside chimneys (i.e. chimneys exposed to 

outdoors below roof line) should not be used unless 

they are:
a) enclosed in a chase, or

b) lined with type B vent pipe, or listed flexible 

vent liner, or other certified chimney lining system

3. Where possible it is recommended to common vent 

boiler and water heater.

4. For multiple boiler installations, consult boiler  

manufacturer for venting recommendations.

Connecting The Vent Damper And Vent 

Connector

Refer to Figure 1, page 2 for size and location of vent 

(flue opening). 

 

NOTICE

Damper blade on furnished vent damper has 1/2 

square inch hole (approximately 3/4” diameter). 

Boilers equipped with intermittent ignition, hole 

should be plugged by using plug supplied with vent 

damper.

1. 

Position furnished vent damper on top of flue outlet 

collar. Fasten damper securely to flue outlet collar with 

sheet metal screws. Verify damper blade has clearance 

to operate inside of diverter. Do not modify either draft 

diverter or vent damper during installation.

As An Option

Damper may be installed in horizontal or vertical 

position, closer to flue outlet collar preferred. See 

Figures 8, 9 and 10 and enclosed vent damper 

instructions.

2. 

Install vent damper to service only single boiler for 

which it is intended. Damper position indicator shall be 

in visible location following installation. Locate damper 

so it is accessible for servicing. See Figure 9.

3. 

Damper must be in the open position when appliance 

main burners are operating.

4. 

Boiler is equipped with factory wired harness that plugs 

into vent damper.

5. 

Slope pipe up from boiler to chimney not less than 1/4” 

per foot.

6. 

Run pipe as directly as possible with as few elbows as 

possible.

7. 

Do not connect to fireplace flue.

8. 

End of vent pipe must be flush with inside face of 

chimney flue. Use a sealed-in thimble for chimney 

connection.

Fasten sections of vent pipe with sheet metal screws 

to make piping rigid. Support horizontal potions of 

vent system to prevent sagging. Use stovepipe wires 

every 5’ to support pipe from above. Use double wall 

vent pipe if vent pipe must go through crawl space. 

Where vent pipe passes through combustible wall 

or partition, use ventilated metal thimble. Thimble 

should be 4 inches larger in diameter than vent pipe.

7 - CHIMNEY AND VENT PIPE CONNECTION

 WARNING

Boiler and venting installations shall be performed 

by a qualified expert and in accordance with the 

appropriate manual. Installing or venting boiler 

or other gas appliance with improper methods or 

materials may result in serious injury or death due 

to fire or to asphyxiation from poisonous gases such 

as carbon monoxide with is odorless and invisible.

!

     

Содержание OMGC-8D

Страница 1: ...INSTALLATION OPERATION MAINTENANCE MANUAL C S A Certified For Natural Gas Or Propane Models OMGC 8D OMGC 8DP OMGC 9D OMGC 9DP An ISO 9001 2008 Certified Company Tested For 50 psi ASME Working Pressure...

Страница 2: ...IONS Table 1 Dimensions BOILER MODEL NUMBER DIMENSIONS INCH FLUE DIAMETER A WIDTH OMGC 8 7 27 OMGC 9 7 30 Add 5 to height for vent Damper Figure 1 Dimensions Minimum acceptable height for Low Water Cu...

Страница 3: ...ments such as intermittent system operation extensive piping systems etc 3 Mbh 1 000 Btuh British Thermal Unit Per Hour Ratings marked Net AHRI Ratings indicate amount of remaining heat input used to...

Страница 4: ...Read this manual and understand all requirements before beginning installation SAFETY SYMBOLS WARNINGS The following defined symbols are used throughout this manual to notify the reader of potential...

Страница 5: ...2 Where required by the authority having jurisdiction the installation must conform to the Standard for Controls and Safety Devices for Automatically fired Boilers ANSI ASME CSD 1 3 Boiler series is...

Страница 6: ...cted indoor spaces All Outdoor Air Provide permanent opening s communicating directly or by ducts with outdoors A Two Permanent Opening Method Provide opening commencing within 12 inches of top and se...

Страница 7: ...igure 2 Use or larger pipe Use pipe suitable for temperatures of 375 F 191 C or greater Individual boiler discharge piping shall be independent of other discharge piping Size and arrange discharge pip...

Страница 8: ...e LOW WATER TEMPERATURE AND LARGE WATER CONTENT SYSTEM See Figures 6 and 7 Page 10 Significant condensation may form in boiler and or venting system if boiler is operated for long period of time with...

Страница 9: ...9 Figure 5 Chilled Water Piping Figure 4 Typical Hot Water Piping 6 CONNECTING SUPPLY AND RETURN PIPING...

Страница 10: ...10 Figure 6 BYPASS PIPING CIRCULATOR ON SUPPLY Figure 7 BYPASS PIPING CIRCULATOR ON RETURN Bypass Piping Required For High Mass Large Water Content Systems 6 CONNECTING SUPPLY AND RETURN PIPING...

Страница 11: ...ugged by using plug supplied with vent damper 1 Position furnished vent damper on top of flue outlet collar Fasten damper securely to flue outlet collar with sheet metal screws Verify damper blade has...

Страница 12: ...fireplace dampers 4 Place in operation the appliance being inspected Follow the lighting instructions Adjust thermostat so appliance will operate continuously 7 CHIMNEY AND VENT PIPE CONNECTION 5 Tes...

Страница 13: ...r indicator points to open position Turn thermostat or controller down again and check damper position indicator returns to closed position Vent Damper Manual Operation Vent damper may be placed in op...

Страница 14: ...ller Two stage regulation should be used by propane installer Propane gas piping should be checked out by propane installer CHECKING GAS PIPING DANGER Fire Hazard Do not use matches candles open flame...

Страница 15: ...ermostat on outside wall 3 Do not install a thermostat where it will be affected by drafts hot or cold pipes sunlight lighting fixtures televisions a fireplace or a chimney 4 Check thermostat operatio...

Страница 16: ...ntegrated High Limit Electronic Ignition Control 240008781 I Inducer is not an option WARNING Modification substitution or elimination of factory equipped supplied or specified components may result i...

Страница 17: ...17 11 WIRING DIAGRAMS Figure 13 Integrated High Limit Electronic Ignition Control 240008781 PILOT FLAME SENSOR...

Страница 18: ...S Figure 14 Integrated High Limit Electronic Ignition Control 240008781 WARNING Modification substitution or elimination of factory equipped supplied or specified components may result in personal inj...

Страница 19: ...repeat this process Repeat until you have covered every radiation units in the system ending up at highest unit in system If your units have automatic vents manual venting is unnecessary but it will...

Страница 20: ...rol knob slightly and turn clockwise to OFF Do not force WARNING If you do not follow these instructions exactly a fire or explosion may result causing property damage personal injury or loss of life...

Страница 21: ...y turning thermostat to lowest setting for one minute then back to normal setting ADJUST PILOT BURNER Pilot flame should surround 3 8 to 1 2 of the pilot sensor See Figure 16 If flame needs adjusting...

Страница 22: ...degrees C After setting limit control to limit setting check to see if it shuts off gas supply to burners Turn your thermostat up to call for heat and let boiler run until temperature of water reache...

Страница 23: ...T PIPE Venting and piping should be checked at least once a season If vent piping shows any sign of leaking replace immediately WATER SYSTEM If system is to remain out of service during freezing weath...

Страница 24: ...inals and wire joints Rollout switch blown Have your service agent check heat exchanged for blockage Replace rollout switch with exact replacement Blocked vent blown Have your service agent check vent...

Страница 25: ...nstalled in supply line It will eliminate air from water before it reaches radiators and bleed off this air MAIN AIR VENT FOR DOWN FLOW SYSTEMS OR DIAPHRAGM TYPE EXPANSION TANK Before system is filled...

Страница 26: ...ed vent safety switch must be reset manually after switch has cooled off by pushing reset button down Check venting system and chimney for blockage when restoring system to operating condition DO NOT...

Страница 27: ...b is fully inserted in well and is not loose Refer to enclosed addendum for wiring instructions when using indirect hot water heater A 3 Adjusting Settings To discourage unauthorized changing of setti...

Страница 28: ...retry Flame signal was lost during state 7 or 8 and delay is called before retry 32 second delay 13 Soft lock out Soft lockout duration is one hour may override with manual reset 14 Hard lock out Man...

Страница 29: ...and display On retry models wait for retry or reset at thermostat Check for correct installation and wiring before replacing any component Control module cannot be repaired If it malfunctions it must...

Страница 30: ...umber of retries exceeded Soft lockout Soft lockout is reset after one hour if alarm reason disappears 63 Soft lockout maximum number of recycles exceeded Soft lockout 64 Soft Lockout electronics fail...

Страница 31: ...nnections are clean and tight Replace damaged wire Check for cracked ceramic insulator which can cause short to ground and replace igniter sensor if necessary At gas valve disconnect main valve wire f...

Страница 32: ...ECR International 2201 Dwyer Avenue Utica NY 13501 web site www ecrinternational com...

Отзывы: