25
7.1
General
Use piping materials and joining methods acceptable
•
to authority having jurisdiction. In absence of such
requirements:
USA - National Fuel Gas Code, ANSI Z223.1/NFPA
•
54
Canada - Natural Gas and Propane Installation Code,
•
CAN/CSA B149.1
Size and install gas piping system to provide suffi cient
•
gas supply to meet maximum input at not less than
minimum supply pressure. See Table 5.
Support piping with hooks straps, bands, brackets,
•
hangers, or building structure components to prevent or
dampen excessive vibrations and prevent strain on gas
connection. Boiler will not support piping weight.
Use thread (joint) compound (pipe dope) suitable for
•
liquefi ed petroleum gas.
Provide sediment trap up stream of gas valve.
•
Install manual main shutoff valve outside of jacket. See
•
fi gure 7-2.
7.2 Conversion Kit Instructions
See Gas Conversion Kit Instructions included with Boiler.
•
CAUTION
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
•
Do not touch any electrical switch; do not use any
•
phone in your building.
Immediately call your gas supplier from a neighbor’s
•
phone. Follow gas supplier’s instructions.
If you cannot reach your gas supplier, call the fi re
•
department.
!
!
7 - GAS SUPPLY PIPING
TABLE 5: GAS SUPPLY PRESSURE
MODEL
Natural Gas
Propane
Min.
Max.
Min.
Max.
050
3.0" w.c.
(0.7 kPa)
13.5" w.c.
(3.3 kPa)
5.0" w.c.
(1.2 kPa)
13.5" w.c.
(3.4 kPa)
075
3.0" w.c.
(0.7 kPa)
13.5" w.c.
(3.3 kPa)
5.0" w.c.
(1.2 kPa)
13.5" w.c.
(3.4 kPa)
100
3.0" w.c.
(0.7 kPa)
13.5" w.c.
(3.3 kPa)
5.0" w.c.
(1.2 kPa)
13.5" w.c.
(3.4 kPa)
150
3.0" w.c.
(0.7 kPa)
13.5" w.c.
(3.3 kPa)
5.0" w.c.
(1.2 kPa)
13.5" w.c.
(3.4 kPa)
200
3.0" w.c.
(0.7 kPa)
13.5" w.c.
(3.3 kPa)
5.0" w.c.
(1.2 kPa)
13.5" w.c.
(3.4 kPa)
7-1 Gas Connection
Note: See Glossary - Piping Table 16
Gas Connection
NOTICE
Use two (2) wrenches when tightening and fi tting
to pipe boiler's threaded fi ttings. Boiler's internal
piping can be damaged if subjected to excessive
torque.
Содержание OLSSC-075
Страница 45: ...45 13 TROUBLE SHOOTING...
Страница 52: ...52 14 WIRING DIAGRAM 14 1 Connection Diagram...
Страница 53: ...53 14 WIRING DIAGRAM 14 2 Schematic Diagram of Ladder Form...
Страница 70: ...70 NOTES...
Страница 71: ...71 Date Service Performed Company Name Tech Initials Company Address Phone...
Страница 72: ...ECR International Inc 2201 Dwyer Avenue Utica NY 13504 4729 web site www ecrinternational com...