13
240011511 REV. C [05/31/2017]
Table A-5 Carlin EZ-LF Oil Burner Set-Up
Carlin EZ-LF Series Oil Burners
(For use with chimney vented units only)
Furnace
Model
Output
BTU/Hr
Burner
Model
Delavan
Nozzle
Pump
Pressure
[PSIG]
Flow
Rate
[USGPH]
Air
Band
Head Bar
Air
Setting
LRF65C
LRFV65C
66,000
EZ-LF
0.50 / 70°B
125
0.55
Single
Slot
0.60 / 0.65
35%
LRF80C
LRFV80C
78,000
EZ-LF
0.50 / 70°B
170
0.65
Single
Slot
0.60 / 0.65
65%
LRF90C
LRFV90C
89,000
EZ-LF
0.65 / 70°B
135
0.75
Two
Slot*
0.75
45%
LRF100C
LRFV100C
100,000
EZ-LF
0.65 / 70°B
170
0.85
Two
Slot*
0.85 / 1.00
45%
* Burner is factory equipped with single slot air band. Replace with furnished two slot air band for 0.75 and 0.85 USGPH
firing rates.
APPENDIX A - CHECK OUT AND ADJUSTMENTS
A.2 Burner Electrodes
Adjustment of electrode tips with respect to each other, nozzle,
burner head is very important to ensure smooth start-ups and to
permit efficient combustion.
Beckett AFG
• Electrode gap: 5/32 inch.
• Distance above horizontal center-line: 1/4 inch.
• Distance ahead of nozzle: 1/8 inch.
• “Z” dimension, distance from front of end cone (head) to
face of nozzle should be 1-3/4 inch.
Beckett NX
• Electrode gap: 5/32 inch.
• Distance above horizontal center-line: 1/4 inch.
• Distance ahead of nozzle: 3/32 inch.
•
Check/adjust zero calibration per Beckett NX oil burner
manual supplied with furnace.
Riello Burners
• Electrode gap: 5/32 inch.
• Distance above horizontal center-line: 13/64 inch.
• Distance ahead of nozzle: 5/64 to 7/64 inch.
Carlin Burners
• Electrode gap: 1/8 inch to 5/32 inch.
• Distance above horizontal center-line: 5/16 inch.
• Distance ahead of nozzle: Flush to 1/16 inch.
A.1 Oil Burner Air Adjustment
Consult oil burner instructions provided in furnace documents
envelope for specific information concerning burner adjustments,
operation and troubleshooting.
Beckett AFG Burner (Chimney Vent)
Adjust air band by loosening locking screw. Re-tighten locking
screw after each adjustment. Locking screw must be tight when
taking combustion readings, as airflow changes when screw is
loosened.
Beckett NX Burner (Direct Vent)
Loosen splined nut on nozzle line one turn. Turn adjustment
screw clockwise to increase air and counter clockwise to decrease
air. Tighten splined nut after obtaining proper setting.
Riello 40F3 Burner (Chimney Vent)
Combustion air is adjusted by removing burner cover. Loosen
screws that secure air adjustment plate. Move adjusting plate
to either increase or decrease combustion air. When proper air
setting is achieved, re-tighten fixing screws. Re-install cover.
Riello 40BF Burner (Direct Vent)
Combustion air can be adjusted with burner cover on. Remove
plastic cover on top right hand side of burner cover. With Phillips
screwdriver turn adjusting screw clockwise to increase air and
counter clockwise to decrease air. When combustion air is set,
reinsert plastic cover.
Carlin EZ-LF (Chimney Vent)
Adjust air band by loosening locking screw. Re-tighten locking
screw after adjustment.