7.0 SERVICE / MAINTENANCE
REGULAR MAINTENANCE
Contact an authorized service representative to check complete operation
at least once a year.
In Canada see CAN/B139, (Maintenance), in United States refer to NFPA 31, for recommended
servicing procedure. Clean flue pipeson a regular basis. Replace flue pipes if there is any sign of
corrosion or other problems. Gaskets should be checked and may have to be replace.
BLOWER REMOVAL
This furnace has a blower sealing system, which is designed to be tight and rattle free. Refer to
the instructions and pictures below.
Step 1:
Remove
breech plate
Step 2:
Remove Baffles
Step 3:
Clean the round
tubes, if needed (use an
2" diameter brush
Step 4:
Remove Burner
Step 5:
Clean combustion
chamber, if needed
HTL HEAT EXCHANGER