Alarms on external unit display
The external unit control board has a two-digit display that shows any active alarms.
The table below shows the external unit alarms.
Error code
Alarm Description
E0
EEPROM malfunction
E2
Communication error between external unit and internal unit
E3
External board communication error
E4
External unit temperature sensor faulty
E5
Compressor power voltage protection
E6
PFC module protection (only for 36K & 48K with 1 phase)
P0
Compressor head temperature protection
P1
High pressure protection
P2
Low pressure protection
P3
Compressor overcurrent protection
P4
Compressor flow temperature protection
P5
Condensation high temperature protection
P6
Module protection
P7
Evaporator high temperature protection
3.1.10
SYSTEM (fig. 41)
The System
icon is used to call up the window showing the software and hardware version of the display (DU) and of the
power board (PU).
3.1.11
COUNTERS (fig. 42)
Touching the counters
icon on the “Menu“ page calls up the window that shows the operating hours of the following components:
• External unit compressor
• Primary circulator
• Water filter
• DHW compressor
• DHW circulation pump
To rest a counter touch the Reset
icon, a window appears requesting the Service password.
3.1.12
DATE/TIME (fig. 43)
Touching the Date/time
icon on the “Menu” page calls up the window for displaying/setting the time, day, month and year
for the system.
The option is present (which can be deactivated) for automatic change between winter/summer time (Auto DST).
3.1.13
PARAMETERS (fig. 44)
Touching the Service
icon on the “Menu” page (for the use of authorised technical staff only) calls up the window for displaying/
setting the parameters once the Service password has been entered.
The Up and Down arrows can be used to scroll through the list and values of 32 parameters.
To set the parameters see the table below that summarises the parameters.
PARAMETER NAME
RANGE
DEFAULT
COMMENTS
"IN/OUT water tempera-
ture control
0 = Control based on T1
(EWT)
1 = Control based on T2
(LWT)"
0,1
1
"When the value is 0 the capacity control shall be based
on the entering water temperature EWT.
When the value is 1 the capacity control shall be based
on the leaving water temperature LWT."
Additional electric
heaters
0,1,2
0
"0 = no stages enabled
1 = 1 stage enabled
2 = 2 stages enabled"
Electric heater activation
delay
0-60 minutes
15 min
Time delay between the heat pump start up and the che-
cking whether to switch ON the first electric heater stage.
If necessary and enabled, the second stage is energized
with 15 minutes delay from first one. (fixed value)
3
Содержание OS-CEBCH36EI
Страница 1: ......
Страница 2: ...2 1 3 2 U H A S G I F C N E T D R N O M U B L V Z ...
Страница 3: ...3 5 4 A B C ...
Страница 4: ...4 7 D D D C A M H G I F E B D L 6 A B 6a A A ...
Страница 6: ...6 16 15 A B E F E G H C D 14 13 C D A B A H B C D E F E G 11 12 B A ...
Страница 10: ...10 B C A D C E F C G 25 27 26 29 28 31 30 ...
Страница 11: ...11 33 32 35 34 36 37 A C D B 2 3 1 E 4 5 6 7 8 9 ...
Страница 12: ...12 39 38 41 40 43 42 45 44 ...
Страница 13: ...13 47 46 49 48 51 50 52 ...
Страница 14: ...14 ...
Страница 38: ...3 ...
Страница 62: ...3 ...
Страница 86: ...3 ...
Страница 87: ...3 ...
Страница 88: ...www olimpiasplendid it info olimpiasplendid it 277415B 1 ...