MODE
Display
LED5
LED1
B
ENGLISH
EN - 16
• This operation must be performed only by the installer or any similarly qual-
ified personnel and in compliance to the current national regulations.
• To prevent the risk of an electric shock it is mandatory to switch off the main
switch before performing the electrical connections or any maintenance op-
eration to the appliances.
to replace the power cord, proceed as follows:
a
. Raise the air suction grille (3) and remove the two screws (3a) (fig. 28).
b
. Extract the right (release using a screwdriver) and left (1a) doors of the front cover, then rotate the flap
(1) and remove the three screws (1b) and the two screws (1c) (fig. 29).
c
. Remove the front cover (fig.30).
d
.
Unscrew the two fixing screws (X2) to remove the front cover of the switchgear (X1) (fig. 31)
.
e
.
Unscrew the two fixing screws (X4)
to remove the top cover of the switchgear
(X3) (fig. 32).
f
. extract the switch towards the exterior of the switchgear
(fig. 34-A).
g
. Unscrew cable clipping clamp (J1) (fig. 33).
h
. Unscrew the cables locking screws of the terminal board
(J2) (fig. 33)
i
. extract the old cable and insert the new one by following the same path.
l
. lock the three poles of the cable in the terminal board
(J2) and tighten the screws (fig. 34).
m
. Lock the cable with the clamp (J1) (fig. 34).
n
. Close the switchgear.
o
. reassemble the front cover of the machine.
This operation must be performed by specialized personnel possessing the requirements indicated
by law.
2.5 - TOP/BOTTOM INSTALLATION CONFIGURATION
The unit can be installed both in the lower part (adjacent to the floor) and in the upper part (adjacent to the
ceiling) of the wall.
Depending on installation (ceiling or floor) it is sufficient to change the electronic configuration so as to opti
-
mize the aperture angles of the air outlet flap.
2.5.1 - Electronic configuration for lower or upper wall installations
Work as follows (see fig. B):
a
. insert the plug in the power socket to power the air conditioner, then
make sure it is switched to stand-by mode.
b
. Press the key
MODE
for more than 10 seconds on the
control panel, until an acoustic signal is emitted.
c
. the
display shows parameter
.
d
. release the key
MODE
and press it again.
e
. The display shows configuration
(ceiling installation)
or
(floor installation).
f
. Press keys
+
or
-
to select the desired configuration.
g
. Press
MODE
to confirm.
h
. Press the key
to exit from the configuration.
Содержание maeStro Pro
Страница 1: ...INVERTER EN INSTRUCTION FOR USE AND MAINTENANCE...
Страница 5: ...M Y 4 5 3...
Страница 6: ...min 300mm 11 8 8 9 B N 8mm 0 3 6 H H 7 6...
Страница 7: ...202 mm G 162 mm 130 mm G 8 6 4 5 1 10 12 11 G F D F G 13 14...
Страница 8: ...6mm 0 24 15 19 17 16 20 18 F E E E...
Страница 9: ...22 23 A A B B 21 W...
Страница 10: ...H H L L 26 28 24 29 25 L L 27 3 3 3a 3a 1 1 1a 1a 1a 1b 1b 1b 1a A A A A A 1c...
Страница 11: ...34 32 33 35 J1 J2 J1 J2 X3 X4 30 31 X1 X2 X2...
Страница 12: ...min 80mm 3 2 41 39 40 F 3 F F2 F1 F F2 F2 F1 F1 8m 315 38 36 37 10 7...
Страница 13: ...43 3 3 42 F 44 45 6 6a min 5 L 1 3 gal...
Страница 14: ...46 47 Y2 Y2 Y3 Y3 Y1...
Страница 47: ...261725A...