Technical Sheet 

Happy Air PLUS  

FTC.1296.00 
Technical Sheet 
Page 4 

www.oli-world.com 

[email protected] 

[email protected] 

 

Millimetres measures 

 

 
Two installation systems:  

 

1. 

Configuration A

 

– One Happy Air in every flat  

2. 

Configuration B 

– Two Happy Air in every flat  

 

 

According to following conditions

 

 

Contemporaneous utilization factor: 100% (all Happy Air systems work at the same 
time)  

 

Vertically installed main pipeline  

 

Constant main pipeline diameter  

 

Outlet residual pressure: 75 Pa  

 

Pipeline roughness: 0.15mm  

 

Flat height: 2.75m  

 

Pipelin length up to the roof aerator: 1.50m Secondary pipelines made of DN 80 
pipes, are 2 m long and include 2 elbows 

 
 

 

 

 

Pipes Laying and Configuration 

 

 

Depends on the chosen configuration of the system 

 

The ventilator connection pipe must be connected to the main pipe, the dimension 
of which must be calculated beforehand and sized as described in the product 
handbook  

 

The connection must be made with 45º branches in order to facilitate expulsion of 
the inhaled air  

 

The connection can be made directly to the soil stack with primary ventilation, as 
long as it is higher than emission points of discharge networks of the stack 

 

In the case of waste systems with parallel ventilation, the connection pipe can be 
connected to the parallel ventilation stack 

 

 