background image

2

© 2021 OJ Electronics A/S

ETN4-1999  

 English

Max. limit temperature

Allows the highest permissible floor temperature to be set for 
wooden and other floor types when control type has been set to 
room sensor with floor limit (AF). 

Min. limit temperature

Allows the lowest permissible floor temperature to be set for tiled 
and other floor types when control type has been set to room sen-
sor with floor limit (AF). 

Limit function

If application (APp) is set to limit (Li), the lowest temperature at 
which heating is to be provided can be set. 

Frost protection

The lowest temperature for frost protection when the function is 
activated via an external signal (See instruction). 
Example: The setpoint is 25 °C.
Frost protection = 8 °C means temp. setting = 8 °C.

Night setback / energy-saving function

The number of degrees the temperature setting is to be reduced. 
The night setback setting must be preceded by a minus sign (-). Is 
controlled via an external signal (See instruction). 
Example: The setpoint is 25 °C. 
Energy-saving function = -5 °C means temp. setting = 20 °C.
Energy-saving function = +3 °C means temp. setting = 28 °C.

Measured floor temperature

Displays actual floor temperature (if a floor sensor is fitted). 

Measured room temperature

Displays actual room temperature. 

Application 

Sets thermostat function. Select the required control type. 

Note: 

* Room sensor not in use.

Floor (F):

   

 The thermostat controls floor temperature 
alone.  
A floor sensor must be fitted. 

Room (A): 

 

The thermostat controls room temperature 
alone. 

Limit (Li):

 

Limit is an on/off function in which the 
required limit is set in Limit low (”Li” 

a

 ”Lo”) 

after selecting the Li option under APp. When 
the recorded temperature is above the tem-
perature specified in ”Li” 

a

 ”Lo”, temperature 

is controlled in the usual way towards the 
user-specified setpoint. If, on the other hand, 
the temperature drops below that specified in 
”Li” 

a

 ”Lo”, the relay cuts out and ”Lo” ap-

pears on the display. 
Limit function (APp 

a

 Li) should be selected if 

a limit is required for when heating is permit-
ted to be activated. Only one sensor is used 
for the limit function, and this sensor must 
be connected to the floor sensor input of the 
thermostat. 

Room/limit (AF):

   The thermostat controls room temperature 

while respecting min. and max. limits for floor 
temperature. A floor sensor must be fitted.

Thermostat with  

sensor for:

APp

a

F

Floor

APp

a

A

Room

APp

a

Li

Limit

APp

a

AF

Room/

floor limit

APp

a

C

Regulator

Floor

x

x

x

Room

x

x

Room and Floor

x

x

x*

x

x

Without

x

THERMOSTAT SETUP MENU

Menu overview

Settings

To set parameter values, press and hold the centremost button for 
three seconds. 

SCA 

 

a

 

 Hi 

 

a

 

40

 will appear on the display. Firstly, 

SCA

 will be displayed for 1 second, followed by 

Hi

, and finally 

40

The required value can now be set using the navigation buttons. To 
access the next parameter, press the programming button again. 
If no button is pressed for 30 seconds, the program returns to the 
initial display.

Max. temperature

The highest temperature to which the thermostat can be set. 

Min. temperature

The lowest temperature to which the thermostat can be set. 

Parameter

Shown on display

Factory settings

Max. temperature

SCA 

a

 Hi 

a

 70

70 °C  

(0,0/+70 °C)

Min. temperature

SCA 

a

 Lo 

a

   -19,5

-19,5 °C 

(-19,5/+60 °C)

Max. limit tempera-

ture FLOOR *1

Li 

a

 Hi 

a

 28

28 °C  

(-19.5/+70 °C + OFF)

Min. limit tempera-

ture FLOOR *1

Li 

a

 Lo 

a

 15

15 °C  

(-19.5/+70 °C + OFF)

Min. limit tempera-

ture Limit function *2

Li 

a

 Lo 

a

   -19,5

-19,5 °C  

(-19.5/+70 °C + OFF)

Frost protection

dEF  

a

 8.0

8 °C  

(0/+10 °C) 

Night setback *3

nSb 

a

 -5.0

-5 °C  

(-19.5/+30 °C)

Measured floor 

temperature

FLo 

a

  24.5 (example) *4

Measured room 

temperature

ro 

a

  21.5 (example) *4

Application

APp 

a

  F  (Floor sensor)

 

a

  A  (Room sensor)

 

a

  Li  (Limit function)

 

a

  AF   (Room  sensor 

with floor tempe-

rature limits)

 

a

  C :   Regulator

F : Floor

Scale

LCd 

a

 C 

C = Celsius

(nU = numerical 0-100 %)

Temperature reading 

in start display

dF 

a

 SP

SP = Setpoint 

(tP = actual temp.)

Adjust offset

Adj 

a

  24.5 (example)

Actual temperature 

(+/- 10 °C) 

Control method 

PWM 

a

 On

On

(OFF)

PWM cycle time *5

cyc 

20

20 minutes

(10-60 min)

Differential tempera-

ture *6

dIF 

a

 0,4

0.4 °C

(0.3/10 °C)

Relay function

rEL 

a

 no 

 no = normally open 

(nc = normally closed)

EN50559

PLi 

a

 0

0 min (0-20 min.)

Software version

SU 

x.xx

*1 : Only available if APp 

a

 AF is selected under Application.

*2 : Only available if APp 

a

 Li is selected under Application.

*3 : Only available with external timer.

*4 : With no or disconnected sensor, - - is shown on the display.

*5 : Only available if PWM is ON under Control Method.

*6 : Only available if PWM is OFF under Control Method.

If Regulator (C) is selected under Application, the floor and room sensors are discon-

nected and heating is controlled on a scale of 0-10, corresponding to 0-100 % of full 

power. 

Содержание ETN4-1999

Страница 1: ...er button Programming ON OFF switch Left button Lower temperature Right button Raise temperature Heating ON Child lock or C Frost protection Temperature set point Night setback Thermostat The ON OFF b...

Страница 2: ...n and max limits for floor temperature A floor sensor must be fitted Thermostat with sensor for APpa F Floor APpaA Room APpa Li Limit APpaAF Room floor limit APpa C Regulator Floor x x x Room x x Room...

Страница 3: ...ced control method which calculates the most effective and economi cal way to heat homes and other buildings ON OFF control is traditional differential control e g 0 3 C for other tasks PWM cycle time...

Страница 4: ...r defective or short circuited terminals 10 11 Replace sensor sensor cable To continue to operate the system without sensor set control type to Regulator under Application APp aC E2 External floor sen...

Страница 5: ...r C Frostschutz Temperatur Sollwert Nachtabsenkung Thermostat Mit dem Ein Aus Schalter wird der Thermostat durch Kippen des Schalterknopfs aus 0 oder eingeschaltet I Bei ausgeschalte tem Thermostat 0...

Страница 6: ...s anzuschlie en ist Raum Grenze AF Der Thermostat regelt die Raumtemperatur mit min und max Grenzen f r die Bodentemperatur Ein Bodenf hler muss montiert sein Thermostat mit Sensor f r APpaF Boden APp...

Страница 7: ...nes Regelprinzip das sich auf die effizienteste und wirt schaftlichste Nutzung ausrichtet und z B zur Wohnungssteuerung angewandt wird Die EIN AUS Regelung ist eine herk mmliche Differenzregelform z B...

Страница 8: ...r kurzgeschlossen Klemme 10 11 F hler F hlerkabel austau schen F r fortgesetzten Betrieb ohne F hler kann der Thermos tat auf Regler unter Anwendung APp a C eingestellt werden E2 Externer Boden f hler...

Страница 9: ...ectronics A S 9 MCS4 10 MSD4 1999 MSA4 10 ETN4 1999 9 9 9 9 10 10 9 10 10 10 10 10 10 10 10 10 11 11 11 11 11 11 11 EN50559 12 12 12 12 ETN4 1999 DIN 19 5 70 C C I 0 0 30 19 5 70 C SCA a Hi Lo Li a Hi...

Страница 10: ...5 C 19 5 60 C 1 Li a Hi a 28 28 C 19 5 70 C 1 Li a Lo a 15 15 C 19 5 70 C 2 Li a Lo a 19 5 19 5 C 19 5 70 C dEF a 8 0 8 C 0 10 C 3 nSb a 5 0 5 C 19 5 30 C FLo a 24 5 4 ro a 21 5 4 APp a F a A a Li a A...

Страница 11: ...11 Li Li a Lo Li APp Li a Lo Li a Lo Lo APp a Li AF C APp a C Night setback 20 60 25 0 60 x 0 25 0 15 15 nSb nSb APp C 100 ETN4 1999 20 100 nSb nSb nSb nSb 30 nSb dEF nSb 0 0 10 0 0 0 SCA aLo 10 0 SC...

Страница 12: ...3 12 13 14 Fax 45 73 12 13 13 oj ojelectronics com www ojelectronics com 12 EN50559 EN 50559 VDE 0705 559 4 EN DIN 0 20 90 10 10 6 10 EN50559 6 EN50559 2 2 1 60 10 APp aF ETN4 1999 OJ Electronics A S...

Страница 13: ...is boutons de navigation permettent une utilisation ais e du menu FONCTIONNEMENT G N RAL Bouton central Programmation Interrupteur ON OFF Bouton de gauche Temp rature plus basse Bouton droit Augmenter...

Страница 14: ...e Affiche la temp rature ambiante r elle Application R gle la fonction du thermostat S lectionnez le type de contr le requis Remarque Sonde d ambiance non utilis e Plancher F Le thermostat contr le un...

Страница 15: ...st activ e La zone gris clair correspond la dur e de fonctionnement relative lorsque la fonction nocturne a t activ e par les valeurs susmen tionn es La valeur par d faut du degr de la fonction noctur...

Страница 16: ...du thermostat Appuyez sur le bouton central et maintenez le enfonc pendant 10 secondes L cran est teint puis rallum L application est affich e l cran APp aF suivi du r glage de la temp rature ETN4 19...

Отзывы: