MODEL / RATED CAPACITY
(kW)3~ 400 V, 50 Hz, PE
7–25
Hermetically sealed device
Yes
To be checked periodically for leaks
(maximum refrigerant charge: 10 CO
2
-eq t)
No
Refrigerant
R-410A
Refrigerant’s PED group (EN 378:2016)
2
Refrigerant’s safety class (EN 378:2016)
A1
Circuit’s PED category (2014/68/EC)
1
Refrigerant’s GWP value
(global warming potential)
2088
Refrigerant charge
g
1800
Refrigerant charge
kg
1.8
Refrigerant charge
CO
2
-eq kg
3758
Refrigerant charge
CO
2
-eq t
3.758
Maximum permissible operating pressure PS
bar g
45
Maximum permissible temperature
°C
135
Minimum permissible temperature
°C
−15
Low pressure switch
Low pressure cutoff setpoint
bar g
3.4 ± 0.5
Pressure reset setpoint
bar g
5.9 ± 0.5
High pressure switch
High pressure cutoff setpoint
bar g
45 ± 1.2
Pressure reset setpoint
bar g
34 ± 2.0
Compressor
Compressor type
Scroll
6.3 Performance data
To view performance data in other conditions, please use the Oilon
Selection Tool (www.oilon.com).
The heat pump’s automation system keeps the compressor’s rotation speed within
the compressor’s operating envelope. The available operating range depends on the
compressor’s rotation speed as well as the evaporator and condenser temperature.
Condenser circuit liquid: water
Evaporator circuit liquid: mix of water and ethanol, 28 mass-% ethanol (34 volume-%)
M8003 2219EN
39 (54)
Содержание ECO Inverter+ 7
Страница 1: ...M8003 2219EN 24 May 2022 INSTALLATION AND COMMISSIONING ECO Inverter 7 25 ...