Domestic hot water settings
DEVICE SETTINGS → HOT WATER
STATUS VIEW → HOT WATER
Setpoints for
operating modes
There are three operating modes for domestic hot water heating:
Normal
,
Boost
,
and
Reduced
.
The
Home/Away
function allows you to select between the
Normal
mode and the
Reduced
mode. With the Schedule function, you can schedule the system to switch
between the
Normal
and the
Reduced
mode on different weekdays and at different
times.
● When the domestic hot water boost function is activated from the
Home
view,
the operating mode will switch to
Boost
(and the tank will be heated up to the
boost temperature).
● The
Boost
function can be used only if using the in-line heater for domestic hot
water heating has been enabled (i.e. the additional heater’s
Mode for heating
setting is either
After compressor
or
With compressor
).
Schedule for
operating modes
See section
Home or Away function and Schedules.
→ SETTINGS
Used
Domestic hot water heating is enabled.
Hot water heating
Off
Domestic hot water heating is disabled.
SETTINGS → LEGIONELLA INHIBITION
This function heats up the domestic hot water to a high temperature to prevent bacterial growth.
Temperature is kept at a high level for a specific period of time (the clean-up period). To achieve sufficient
temperature levels, the domestic hot water in the tank can be heated up using both the compressor and
the unit’s electric immersion heater.
● If domestic hot water temperature remains mostly at or above +55 °C, this function is usually not
necessary.
● The boost function can be used only if using the electric immersion heater for heating domestic hot
water has been enabled (i.e. the additional heater’s
Mode for heating
setting is either
Legionella
inhibition,
After compressor
or
With compressor)
.
Off
Legionella inhibition is disabled.
Legionella inhibition
Used
Legionella inhibition is enabled.
Time between starts
The interval between heating periods. This interval depends on the domestic hot
water temperature setting.
● If domestic hot water is usually kept only at a lukewarm temperature, use a
shorter interval.
● Usually, the interval should be set to 3–7 days.
Inhibit start time
The time of day at which the function is activated. Select a time when domestic hot
water is not typically used, such as nighttime hours.
Time to next start
The number of days (d) before the function is activated again.
3.5 Other settings
Device settings → Controller time
If the data hub is connected to the internet, the current time is retrieved automatically. If there is no
internet connection, set the time by hand.
Time zone
The current time zone (UTC; 2 h in Finland).
Day light saving
No
The system does not adjust automatically for daylight saving time.
18 (31)
M8004 2123EN