3.

 

Mounting 

3-1 Caution 

Danger

 

 

For prevention of electrical shock, power supply to the control panel should be 

disconnected before installation work. 

 

Caution

 

 

For installation, do not use any parts other than originally supplied ones.   

Failure to this may result in injury or breakdown of the cooling unit. 
In case screws are used for installation instead of the original bolts, 

put a plate between the screw and the cap nut so as the direct torque not to 

be transmitted. Or, the cap nut may cause slipping. 

 

Cut out the mounting surface of the enclosure as specified in the drawing of page 8. 
 

 

COOLCABI must be placed horizontally and   

perpendicularly within a tolerance of 

±

2

  in order 

to keep stable operation of the unit and 

to make a smooth drainage. 

 

 

 

Locate  the  unit  so  as  to  assure  good  ventilation 

and distance of at least 200mm from the walls or 

other units.   

Also,  there  should  be  no  hindrance  to  the  air 

circulation inside the control panel. 

Failure  to  the  above  may  result  in  poor  cooling 

performance or condensation.   

 

The supply voltage must be as specified on the rating 

plate of the unit. 

Electrical connection should be made via appropriate   

circuit breakers as shown in the right. 

Ground  the  wire  without  fail  to  prevent  electrical 

shocks 

Electrical works required for installation of the unit must be done only 

by specialists. Improper installation may result in electrical shocks or fires. 
For protection of the compressor, wait at least 30 minutes after installation before 

connecting power to start operation. 

 
 
 

Hermetically seal the control panel all round. 

Inferior sealing may cause condensation which lead to poor cooling efficiency. 

Put covers on the components inside the enclosure to protect them from cutting 

dust during installation work. 

[Short circuit] 

Electric  components  or  other  objects  near  the  cool 

air outlet may disturb cool air circulation. If the cool 

air  hit  against  them,  it  will  directly  return  to  the 

suction port without being distributed to the whole 

area in the enclosure. This causes not only troubles 

of  the  components  but  may  negatively  affect 

operation  of  the  cooling  unit  which  lead  to 

overcurrent and product failure. 

In  case  such  short  circuit  is  found  during  cooling 

operation,  improve  the  environment  by  attaching 

rectifying  plates  or  installing  agitation  fans  as 

necessary. 

COOLCABI 

Enclosure  Enclosure 

COOL 
CABI 

Earth 

Breaker for 
Leakage 

R  S 

COOL 
CABI 

Rectifying 
plate 

Agitation fan 

Control equipment 

COOLCABI 

Cool 
air 

200mm or more 

Enclosure 

COOLCABI 

Wall, 
other units 

200mm 
or more 

Содержание Cool Cabi OCA-S1300BCD-A200

Страница 1: ...OCA S350BCD A200 OCA S700BCD A200 OCA S1300BCD A200 OCA S2300BCD A200...

Страница 2: ...2 20 50 85 RH 70...

Страница 3: ...3 OCA S1300BCD A200 OCA S1300BCD A200 14 35 85 RH 3...

Страница 4: ...4 M6 2 200mm 30...

Страница 5: ...5 P 6 P 7 OCA S1300BCD A200 OCA S700BCD OCA S1300BCD OCA S2300BCD A200...

Страница 6: ...6 OCA S350BCD A200 OCA S700BCD A200 OCA S1300BCD A200 OCA S2300BCD A200...

Страница 7: ...7 OCA S350BCD A200 OCA S1300BCD A200 35 85 RH...

Страница 8: ...8 OCA S350BCD A200 OCA S700BCD A200 1 4 OCA S1300BCD A200 OCA S2300BCD A200 OCA S1300BCD 4 OCA S2300BCD 8...

Страница 9: ...A S350BCD A200 OCA S700BCD A200 OCA S1300BCD A200 OCA S1300BCD A200 OCA S350BCD A200 OCA S700BCD A200 OCA S1300BCD A200 OCA S2300BCD A200 a 240V 1 5A 2 P 13 14 AC200V IN L N E 1 2 3 a 240V 1 5A 2 P 13...

Страница 10: ...10 OCA S2300BCD A200 1 30mA...

Страница 11: ...11 30 ON OFF 1 6 ON OFF ON OFF P 12 35 Set Up Down 35 30 45 Set Up Down 3 30 Down Up Set ALARM Set Down Up RUN...

Страница 12: ...3 Set Up Down Set 5 3 10 1 6 ON OFF 30 0 99 Up Down 3 45 35 51 2 1 20 0 0 99 0 1 99 1 100 1 99 9900 24 412 0 0 1 0 1 0 0 1 0 P 17 6 1 2 1 P 17 6 1 2 1 0 1 OPEN CLOSE OPEN CLOSE 0 1 0 0 0 3 0 1 2 3 P...

Страница 13: ...13 P 15 16 0 0 1 OPEN CLOSE 0 1 0 1 2 3 P 13 14 1 0 3 0 1 2 3 7 7 60 3 3 3 10 ON OFF Set 3 30 Set 3 AS Ao 1 2 2 3 OPEN 0 8 AS 0 AS 1 AS 2 AS 3...

Страница 14: ...E3 E4 CLOSE E5 SE OPEN E1 E3 E4 OPEN 3 E3 E5 SE CLOSE E1 E4 CLOSE E3 E5 SE OPEN E1 E4 OPEN E4 P 12 0 Ao 1 AS 1 2 2 3 0 OPEN CLOSE CLOSE OPEN 1 OPEN CLOSE CLOSE OPEN 2 E5 SE OPEN E1 E3 E4 OPEN E5 SE C...

Страница 15: ...15 35 5 35 30 4 P 14 3 30 1 30 5 35 30 ON OFF ON OFF 35 30 ON OFF ON OFF...

Страница 16: ...16 7 3 5 5 35 30 ON OFF ON OFF 30 35 45 ON OFF ON OFF...

Страница 17: ...17 45 P 14 43 P 14 Set 3 P 14 Set 1 P 14 OFF...

Страница 18: ...300BCD OCA S2300BCD OCA S1300BCD A200 OCA S350BCD A200 FM 350BCDIN 200V FM 350BCDOUT 200V OCA S700BCD A200 FM 700BCDIN 200V FM 700BCDOUT 200V OCA S1300BCD A200 FM 1300BCDIN 200V FM 1300BCDOUT 200V OCA...

Страница 19: ...19 OCA S1300BCD A200 P 18 OCA S1300BCD A200 35 85 RH OCA S350BCD OCA S700BCD OCA S1300BCD OCA S2300BCD...

Страница 20: ...20 OCA S2300BCD A200 50 45 P 11 P 4 P 18 19 P 19 OFF No 7 5kW 1 4 P11 5 4...

Страница 21: ...960 1150W 2 270 295W 455 510W 760 875W 1160 1390W 100W 250W 400W 650W 4 20 50 85 RH A 62dB 65dB 65dB 68dB 4 30 45 35 35 85 RH 1a 240V 1 5A 2 COMMON 10 150Hz 1 0G 20 IP54 EMC EN61000 6 2 EN61000 6 4 EN...

Страница 22: ...22 OCA S350BCD A200 OCA S700BCD A200 12 12 2 M8 13 4 M6 14 4 M6 14...

Страница 23: ...23 OCA S1300BCD A200 OCA S2300BCD A200 12 12 2 M8 13 4 M6 14 2 M8 13 6 M8 14...

Страница 24: ...24 1 13 64 19 10 4 431 1304 7000 21 TEL 053 522 5572 FAX 053 522 5573 8 2019 5...

Страница 25: ...ents 1 Safety Precautions 2 Part names and evaporation mechanism 3 Mounting 4 Wiring 5 Operation 6 Alarm Safeguard 7 Maintenance 8 Specifications 9 Warranty period 10 Waste disposal Please read this b...

Страница 26: ...in short life or damage of the unit Shocks and vibrations should be strictly avoided at the site of use Never tamper or repair the main body Please consult with your local supplier for repairing servi...

Страница 27: ...mperature Evaporation fin and the external air that passes through the fin the water vaporizes into the atmosphere Meanwhile such evaporation takes heat away from the surroundings and it brings about...

Страница 28: ...as shown in the right Ground the wire without fail to prevent electrical shocks Electrical works required for installation of the unit must be done only by specialists Improper installation may result...

Страница 29: ...nd the nuts from inside the control panel and secure them 6 To ensure keep the panel interior airtight caulk the gaps completely if any 7 Apply the enclosed Alarm description label to an appropriate p...

Страница 30: ...6 Cutouts for mounting View from outside the panel OCA S350BCD A200 OCA S700BCD A200 OCA S1300BCD A200 OCA S2300BCD A200...

Страница 31: ...deg C and humidity not exceeding 85 RH for both ambient and enclosure interior When the evaporation fin or the evaporation sheet is dirty When passing air volume in evaporation mechanism declined due...

Страница 32: ...is hooked Unscrew first and then lift up the panel to remove 2 Detach the Maintenance panel by removing 4 screws 3 Absorb the water in the Evaporation pan and the Water pan with a syringe or a wiping...

Страница 33: ...ured 6 For the application using crimp terminals the bar terminals made by Phoenix Contact 4 2 Circuit diagram OCA S350BCD A200 OCA S750BCD A200 OCA S1300BCD A200 Example OCA S1300BCD A200 The number...

Страница 34: ...e made so as to assure stable operation without affected by such current as well as providing effective protection against possible overcurrent thereafter b For earth leakage breakers use a reference...

Страница 35: ...ting temperature Caution Setting temperature should be basically at 35 Avoid setting at an unnecessarily low value which may cause excessive ondensation or drainage 1 Turn on the unit The current inte...

Страница 36: ...tting range 0 99 This is the function to remind you maintenance works in a timely manner 0 This function is ineffective 1 99 1 means 100 hours Notification period can be set between 100 to 9900 hours...

Страница 37: ...eriod for restarting the compressor after shutdown For prevention of frequent ON OFF of the compressor cooling operation is suspended during the set period Display of software version This is to displ...

Страница 38: ...E3 E5 and SE OFF OPEN Alarm E1 and E4 OFF OPEN Alarm E4 is not output when Fo is set at 0 See page 12 Assignment table of Alarm output terminals Ao 1 AS Terminals 1 2 Terminals 2 3 Description Operati...

Страница 39: ...eration will not start for a certain period of time initial setting 3 min after cooling operation has stopped even if the internal temperature goes up to the set temperature 1 Continuous run Cooling o...

Страница 40: ...he air is not circulated by the internal fan For protection of the refrigerant circuit the internal fan will not stop for 5 minutes after cooling operation has stopped The internal fan runs continuous...

Страница 41: ...See the assignment table of alarm output terminals in page 14 Current internal temperatures and E4 are displayed by turns to remind you to carry out maintenance work Cooling operation will be continu...

Страница 42: ...0BCD CF S2 2 pcs set OCA S2300BCD 7 2 Replacement of external fan Example OCA S1300BCD A200 In the event of a fan failure go through the following steps to replace the fan 1 Remove the suction port fi...

Страница 43: ...orking condition is within the specified range 35 deg C 85 RH both inside and outside an enclosure the Evaporation fin or the Evaporation sheet may be contaminated Carry out maintenance work according...

Страница 44: ...here temperature exceeds 45 f Clean the filter g Check temperature setting and the internal temperature In case of fan failure replace the fan h To check whether the fan works properly execute forcibl...

Страница 45: ...ection External output Alarm output 1a 240V 1 5Ax2 Output Common Vibration resistance Vibratility 10 150Hz Acceleration 1 0G Sweep cycle 20 times Protective category Equivalent to IP54 for internal ci...

Страница 46: ...arm air Air from outside Cool air Air from inside External suction port filter white Evaporation sheet Terminal board Bottom view 4 M6 Depth 14mm For fixing bolt Top view 2 M8 Depth 13mm For eyebolt A...

Страница 47: ...ottom view Top view Air from outside Warm air 2 M8 Depth 13mm For eyebolt External suction port filter white Drain pipe outer dia 12mm Evaporation sheet Cool air Air from inside Terminal board 6 M6 De...

Страница 48: ...user Recovery of the refrigerant should be done by an authorized waste disposer Owner s management responsibility Check of equipment The enclosure cooling unit needs simple regular inspection Daily c...

Отзывы: