Parameter
Notation
Default
Value
Parameter Description
Range
Alarm function for
alarm output
2
ALFN
0
: No alarm function
1
: Dwell timer action
2
: Deviation high alarm
3
: Deviation low alarm
4
: Deviation band out of band alarm
5
: Deviation band in band alarm
6
: Process value high alarm
7
: Process value low alarm
Alarm operation mode
ALMD
0
: Normal alarm action
1
: Latching alarm action
2
: Hold alarm action
3
: Latching & Hold action
Hysteresis contol of alarm
ALHY
Low: 0.1
High:
50.0 C
(90.0 F)
B
B
0.1 C
(0.2 F)
B
B
0
Alarm failure transfer mode
ALFT
0
: Alarm output ON as unit fails
1
: Alarm output OFF as unit fails
0
COMM
Communication function
0
: No communication
1
: Modbus RTU mode protocol
1
2
:4-20mA retransmission output
3
:0-20mA retransmission output
:0-5V retransmission output
4
:1-5V retransmission output
5
:0-10V retransmission output
6
BAUD
Baud rate of digital
communication
2
0
: 2.4 Kbits/s
1
: 4.8 Kbits/s
2
: 9.6 Kbits/s
3
: 14.4 Kbits/s
4
: 19.2 Kbits/s
5
: 28.8 Kbits/s
6
: 38.4 Kbits/s
ADDR
Address assignment of
digital communication
Low: 1
High: 255
DATA
Data bit count of digital
communication
0
: 7 data bits
1
: 8 data bits
1
PARI
Parity bit of digital
communication
1
: Odd parity
2
: No parity bit
0
: Even parity
0
STOP
Stop bit count of digital
communication
1
: Two stop bits
0
0
: One stop bit
RELO
Retransmission low scale
value
Low: -19999
High: 45536
(0.0 °C)
32.0 °F
REHI
Retransmission high scale
value
Low: -19999
High: 45536
212.0 °F
(
)
100.0 °C
11-1