Dry contact
OFF voltage
User define for the 24V system: 21.6~32.0V
Step size: long press for 1V
,
short press for 0.1V
AGM
(Default)
/GEL/FLD: 24.0V
LFP8: 24.0V
LCNM7: 24.5V
User define for the 48V system: 43.2~64.0V
Step size: long press for 1V
,
short press for 0.1V
AGM
(Default)
/GEL/FLD: 48.0V
LFP15: 45.0V
LFP16: 48.0V
LCNM14: 49.0V
21
Maximum
charging
current
IC-24/3000/100/80
: 100A
(Default)
User define: 5~100A
IC-48/5000/80/60
: 80A
(Default)
User define: 5~80A
Step size: long press for 50A
,
short press for 5A
22
Max. utility
charging
current
IC-24/3000/100/80
: 80A
(Default)
User define: 2~80A
IC-48/5000/80/60
: 60A (
Default)
User define:
2~60A
Step size: long press for 10A, short press for 1A
24
Clear fault
OFF
(Default)
ON
25
Clear the
PV
accumulate
d energy
OFF
(Default)
ON
26
Battery
capacity
100AH
(Default)
User define:1~4000AH
Step size:
Below 200AH: long press for 10A, short press for 1A
Above 200AH: long press for 50A, short press for 5A
CAUTION: To accurately display the battery capacity,
the customer needs to set this item according to the
actual battery capacity.
27
Temperatur
e
compensat
3
(Default)
0 (lithium battery)
0~9 (non-lithium battery)